C C h h a a p p t t e e r r 7 7 P P r r o o d d u u c c t t S S p p e e c c i i f f i i c c a a t t i i o o n n s s
This section provides the following specifications:

Model Numbers

Battery specifications
Environmental and safety specifications
7 7 . . 1 1
M M o o d d e e l l N N u u m m b b e e r r s s
The Integrated Battery Cabinet (IBC) is available in two model to meet the needs of the Eaton 93PM UPS
product line.
Integrated Battery Cabinet (IBC) Models
Eaton 93PM Integrated Battery Cabinet-Large (IBC-L)
Eaton 93PM Integrated Battery Cabinet-Large High Rate (432V)
Eaton 93PM Integrated Battery Cabinet-Large High Rate (480V)
7 7 . . 2 2
S S p p e e c c i i f f i i c c a a t t i i o o n n s s
The following sections detail the battery specifications and the environmental and safety specifications for the
UPS.
7 7 . . 2 2 . . 1 1 B B a a t t t t e e r r y y S S p p e e c c i i f f i i c c a a t t i i o o n n s s
IBC Battery Types
Number of Strings
Battery Replacement
Protection
The shelf life for the batteries installed in the IBC are 6 months from the date code on the battery for the B37
batteries, 8 months from the date code on the battery for the E39 and E54 batteries, and 24 months from the
date code on the battery for the N54 and H41batteries. The recharge date is also stated on a label inside the
IBC.
Failure to recharge the batteries before the expiration of the shelf life will result in reduced discharge time,
shorter float service life, and will void the warranty.
Eaton 93PM Integrated Battery Cabinet (IBC-L, IBC-LH [432V], and IBC-LH [480V]) Installation Manual 164000228—Rev 08
IBC-L: E39, 390 W/cell battery, valve-regulated lead-acid (VRLA) with a 3-year float
service life at 77°F (25°C)
IBC-L: E54, 540 W/cell battery, valve-regulated lead-acid (VRLA) with a 3-year float
service life at 77°F (25°C)
IBC-LH: N54, 540 W/cell battery, valve-regulated lead-acid (VRLA)
IBC-LH: H41, 414 W/cell battery, valve-regulated lead-acid (VRLA)
IBC-LH: H37, 400 W/cell battery, valve-regulated lead-acid (VRLA)
1 string
Must be replaced by a qualified service technician
IBC-L output protected by 300A circuit breaker.
IBC-LH output protected by 500A circuit breaker.
CAUTION
Description
IBC for Eaton 93PM 50 kW UPS
IBC for Eaton 93PM 100 kW UPS
IBC for Eaton 93PM 150 kW UPS
IBC for Eaton 93PM 200 kW UPS
IBC for Eaton 93PM 400 kW UPS