Figure 23. DC Power Terminal Detail – Eaton 93PM IBC-LH (480V)
Ground Terminals
IBC DC (+) Output
to UPS Positive
Terminal (+)
4 4 . . 3 3 . . 2 2 S S t t a a n n d d a a l l o o n n e e P P o o w w e e r r W W i i r r i i n n g g
NOTE 1
NOTE 2
Use this procedure to wire standalone 93PM Integrated Battery Cabinets to the 93PM UPS cabinet.
To install wiring to connections:
1.
Verify the UPS system is turned off and all power sources are removed. Refer to the applicable Eaton
93PM UPS Installation and Operation manual, listed in paragraph
operating procedures.
2.
Open the front door by lifting the latch from the bottom and turning to the right (counterclockwise) and
swing the door open.
46
Eaton 93PM Integrated Battery Cabinet (IBC-L, IBC-LH [432V], and IBC-LH [480V]) Installation Manual 164000228—Rev 08
Standalone IBC installations with three or four IBCs require a customer supplied external
tie point and circuit breaker or disconnect between the IBCs and the UPS.
Up to four IBCs can be installed in a standalone configuration.
TRAY 10
1.7 For More
Information, for UPS
IBC DC (-) Output
to UPS Negative
Terminal (-)