Figure 31. Interface Terminal Detail – Eaton 93Pm Ibc-Lh (480V) - Eaton IBC-L Installation Manuals

93pm integrated battery cabinet-large and large high rate
Hide thumbs Also See for IBC-L:
Table of Contents

Advertisement

Figure 31. Interface Terminal Detail – Eaton 93PM IBC-LH (480V)
1
TB2
or
TB3
10
11
12
NOTE 1
TB2 and TB3 terminals are wired together and are identical. TB2 is located at the bottom
of the IBC and TB3 is located at the top of the IBC. Use TB2 for line-up-and-match shunt
trip, and for standalone bottom entry shunt trip and battery detect connections to the
UPS. Use TB3 for connections between multiple IBCs, for line-up-and-match battery
detect, and for standalone top entry shunt trip and battery detect connections to the
UPS.
NOTE 2
TB2 and TB3 connector pin 1 is located at the front of the cabinet.
NOTE 3
The Thermal Sensor is optional. If not installed, terminals TB2-11, TB2-12, TB3-11, and
TB3-12 are not present.
4 4 . . 5 5 . . 2 2 I I n n s s t t a a l l l l i i n n g g B B a a t t t t e e r r y y S S h h u u n n t t T T r r i i p p I I n n t t e e r r f f a a c c e e C C o o n n n n e e c c t t i i o o n n s s
NOTE 1
Disconnect terminal block plug from terminal block to wire plug.
NOTE 2
Because of the battery shunt trip wiring route in the 93PM UPS cabinet, the wiring from
the IBC shunt trip terminals to the UPS must use wire rated for 600V and Class 1 wiring
methods.
NOTE 3
If the inter-cabinet wiring access pass-through is not used to install the battery shunt trip
interface wiring connections, conduit must be installed between the battery cabinet and
the UPS cabinet.
To install wiring:
1.
If wiring the IBC shunt trip interface terminals using the line-up-and-match inter-cabinet wiring access
pass-through (see
Figure
top entry access, proceed to
access, proceed to
Step
Eaton 93PM Integrated Battery Cabinet (IBC-L, IBC-LH [432V], and IBC-LH [480V]) Installation Manual 164000228—Rev 08
IBC
Optional
15) proceed to
Step
2; if wiring the IBC shunt trip interface terminals using the
Step
4; if wiring the IBC shunt trip interface terminals using the bottom entry
7.
Battery Shunt Trip (+)
Battery Shunt Trip (-)
Not Used
Battery Detect
To Next IBC TB3-4 (Battery Detect Common)
To Next IBC TB3-1 (Battery Shunt Trip +)
To Next IBC TB3-2 (Battery Shunt Trip -)
Not Used
Not Used
Not Used
Thermal Sensor Return
Thermal Sensor
Installation