NOTE
The batteries are rated for a 25°C (77°F) ambient temperature to extend their useful life.
Maximum Relative Humidity: 95%, noncondensing
It is recommended for optimal battery life and discharge performance to keep the ambient air temperature the
battery is used in at 25°C (77°F). Operating temperatures above the recommended range will result in
decreased battery life and performance, and will reduce or void the battery warranty. Refer to Eaton's Terms
and Conditions of Sale with Battery Replacement Coverage and the Battery Replacement Price Book for more
information. These documents can be found at
representative for information on how to obtain copies.
The shelf life for the batteries installed in the IBC is 12 months from the date code on the battery. The recharge
date is also stated on a label inside the IBC.
Failure to recharge the batteries before the expiration of the shelf life will result in reduced discharge time,
shorter float service life, and will void the warranty.
The IBC operating environment must meet the weight requirements shown in
the size requirements shown in
Specifications are subject to change.
Table 1. IBC-L Cabinet Weights
Model
Eaton 93PM Integrated Battery Cabinet-Large
with E54 Batteries
Eaton 93PM Integrated Battery Cabinet-Large
with E39 Batteries
Eaton 93PM Integrated Battery Cabinet-Large
with E28 Batteries
Eaton 93PM Integrated Battery Cabinet-Large
with E54 Batteries and sidecar
Eaton 93PM Integrated Battery Cabinet-Large
with E39 Batteries and sidecar
Eaton 93PM Integrated Battery Cabinet-Large
with E28 Batteries and sidecar
14
Eaton 93PM Integrated Battery Cabinet (IBC-L, IBC-LH [432V], and IBC-LH [480V]) Installation Manual 164000228—Rev 08
Emergency lighting and power equipment battery cabinets (UL924) are rated for
operation in a 20°–30°C (68°–86°F) temperature environment.
www.eaton.com/powerquality
Figure 4
through
Shipping
2189 (4827)
1761 (3883)
1467 (3234)
2231 (4919)
1803 (3975)
1508 (3326)
CAUTION
CAUTION
Figure
9. Dimensions are in millimeters (inches).
Weight kg (lb)
Installed
2144 (4727)
1716 (3783)
1422 (3134)
2186 (4819)
1758 (3875)
1463 (3226)
or contact your service
Table
1,
Table
2, or
Table 3
Point Loading
7 at 306 (675)
7 at 245 (540)
7 at 203 (448)
7 at 312 (688)
7 at 251 (554)
7 at 209 (461)