Figure 30. Interface Terminal Detail – Eaton 93Pm Ibc-L (432V) Or 93Pm Ibc-Lh (432V) - Eaton IBC-L Installation Manuals

93pm integrated battery cabinet-large and large high rate
Hide thumbs Also See for IBC-L:
Table of Contents

Advertisement

Installation
Table 12. IBC TB2 or TB3 Interface Wiring Terminal Block Terminations
Terminal Function
Shunt Trip
Battery Detect
Thermal Sensor
Figure 30. Interface Terminal Detail – Eaton 93PM IBC-L (432V) or 93PM IBC-LH (432V)
TB2
or
TB3
NOTE 1
NOTE 2
NOTE 3
56
Eaton 93PM Integrated Battery Cabinet (IBC-L, IBC-LH [432V], and IBC-LH [480V]) Installation Manual 164000228—Rev 08
Tightening
Torque Nm (lb
Size of Pressure
in)
Termination
#26–#16
0.4 (3.5) - 0.8 (7.1)
#26–#16
0.4 (3.5) - 0.8 (7.1)
#26–#16
0.4 (3.5) - 0.8 (7.1)
IBC
1
10
11
12
20
Optional
TB2 and TB3 terminals are wired together and are identical. TB2 is located at the bottom
of the IBC and TB3 is located at the top of the IBC. Use TB2 for line-up-and-match shunt
trip, and for standalone bottom entry shunt trip and battery detect connections to the
UPS. Use TB3 for connections between multiple IBCs, for line-up-and-match battery
detect, and for standalone top entry shunt trip and battery detect connections to the
UPS.
TB2 and TB3 connector pin 1 is located at the front of the cabinet.
The Thermal Sensor is optional. If not installed, terminals TB2-11, TB2-12, TB3-11, and
TB3-12 are not present.
Type
Screw
Comments
Slotted
Use #18 AWG twisted-pair wires for each input
and return or common. Strip wire insulation
back 10 millimeters to wire terminal blocks.
Use wire rated for 600V and Class 1 wiring
methods.
Slotted
Use #18 AWG twisted-pair wires for each input
and return or common. Strip wire insulation
back 10 millimeters to wire terminal blocks.
Slotted
Use #18 AWG twisted-pair wires for each input
and return or common. Strip wire insulation
back 10 millimeters to wire terminal blocks.
Battery Shunt Trip (+)
Battery Shunt Trip (-)
Not Used
Battery Detect
To Next IBC TB3-4 (Battery Detect Common)
To Next IBC TB3-1 (Battery Shunt Trip +)
To Next IBC TB3-2 (Battery Shunt Trip -)
Not Used
Not Used
Not Used
Thermal Sensor Return
Thermal Sensor