Figure 3. Eaton 93PM 100 kW UPS and Two 93PM Integrated Battery Cabinets
1 1 . . 2 2
O O p p t t i i o o n n a a l l T T h h e e r r m m a a l l S S e e n n s s o o r r
Thermal runaway protection for VRLA batteries can be provided by installing an optional thermal sensor inside
the battery cabinet.
The sensor is wired to an UPS building alarm programmed to turn the charger off when a trip signal is received.
The thermal sensor will maintain the trip state until the temperature it is reset by service. Service should be
called to inspect the batteries and reset the sensor in case of such an event.
1 1 . . 3 3
M M o o d d e e l l C C o o n n f f i i g g u u r r a a t t i i o o n n s s
The following model configurations are available:
93PM Integrated Battery Cabinet-Large
Line-up-and-match or bottom entry standalone.
Contains one battery string to be used with 93PM UPS systems.
Available E28, E39 or E54 batteries.
Up to four IBC-Ls can be paralleled to extend the run time. Use with a 93PM 20-50 kW UPS, 93PM 20-
100 kW UPS, 93PM 20-150 kW UPS, or 93PM 20-200 kW UPS.
Up to eight IBC-Ls can be paralleled to extend the run time. Use with a 93PM 100-400 kW UPS
Eaton 93PM Integrated Battery Cabinet (IBC-L, IBC-LH [432V], and IBC-LH [480V]) Installation Manual 164000228—Rev 08