Table 5. Line-Up-and-Match External Power Wiring Recommendations – Eaton 93PM IBC-L and 93PM IBC-LH
Model
93PM IBC-L
93PM IBC-
LH
NOTE
24
Eaton 93PM Integrated Battery Cabinet (IBC-L, IBC-LH [432V], and IBC-LH [480V]) Installation Manual 164000228—Rev 08
Number of
UPS Model
Cabinets
50 kW
100 kW
1, 2, 3, or 4
150 kW
200 kW
1, 2, 3, 4, 5, 6, 7,
400 kW
or 8
50 kW
100 kW
1 or 2
150 kW
200 kW
400 kW
1, 2, 3, or 4
Standalone IBC-L installations with three or more IBCs or IBC-LH installations with two
or more IBCs require a customer supplied external tie point and circuit breaker or
disconnect between the IBCs and the UPS.
Battery Cabinet to UPS
Recommended Conductor Size
(AWG or kcmil)
Terminal
Battery (+)
Factory Supplied
Battery (–)
Factory Supplied
Ground
Battery (+)
Factory Supplied
Battery (–)
Factory Supplied
Ground
Number per Pole
1
1
#4
one per
cabinet
2
2
#1
one per
cabinet