Battery Settings
The Battery Settings Menu provides control of battery tests, warnings and modes.

Figure 67. Battery Settings Menu

Select Battery Settings
Settings
Local Settings
In/Out settings
On/Off settings
Battery settings
Input signals
Comm settings
User password enable
User password settings
[Auto detection]
[Manual EBM set.]
[Manual battery set.]
Default Value: [Auto detection]
Using standard EBM, UPS detects
automatically the number
of EBM connected
Select Battery Tests
and Warnings
Battery settings
ABM On Off
Auto battery test
Low battery warning
Restart batt. Level
Low BTR warning
External battery
Deep disch.protect.
Battery settings
Auto battery test
Low battery warning
Restart batt. level
Low BTR warning
External battery
4–20kVA Users Guide P-164000669 4–20kVA Users Guide P-164000669—Rev 09
ABM On Off
Enabled
Disabled
Auto battery test
Enabled
Disabled
Low battery warning
%
20
Restart batt.level
%
00
Low BTR warning
180
sec
External battery
Auto Detection
Auto Detection
Auto Detection
Manual EBM set.
Manual batt. set.
External battery
Auto Detection
Manual EBM set.
Auto Detection
Manual EBM set.
Manual batt. set.
External battery
Auto Detection
Manual batt. set.
Auto Detection
Manual EBM set.
Manual batt. set.
Deep. Disch.Protect.
Warranty void if no
No
Yes
Display Menu Screens
Advanced Battery Mode
[Enabled] [Disabled]
In ABM cycling mode:
[No test] [Every ABM cycle]
In constant charge mode:
[No test] [Every day]
[Every week][Every month]
Default Value: [Every ABM cycle]/[Every
week]
[Capacity] [0%] ... [100%]
[Runtime] [0min] ... [60min]
The alarm triggers when the
set percentage of battery capacity
or remaining back-up time is reached.
Default Value: [20%] [3min]
[0%]...[100%]
If set, automatic restart will
occur only when percentage
of battery charge is reached.
Default Value: [0%]
Low Battery Warning:
Below 3 min. or less than
setting capacity thershold.
Default Value: [0%]
External battery
1 BM
External battery
0 Strings
External battery
0 AH
[Yes] [No]
If set to Yes, the UPS automatically
prevents battery from deep
discharge by adapting end of
back-up time voltage threshold.
Warranty void if set to No.
Default Value: [Yes]