In/Out Settings
The In/Out Settings menus allows control of input and output limits.

Figure 65. In/Out Settings Menu

Settings
Local Settings
In/Out settings
On/Off settings
Battery settings
Input signals
Comm settings
User password enable
User password settings
In/out settings
Output voltage
High Efficiency mode
Protected Bypass
Overload prealarm
Redundancy
Byp freq limit
Byp volt min limit
Byp volt max limit
4–20kVA Users Guide P-164000669 4–20kVA Users Guide P-164000669—Rev 09
Display Menu Screens
Output voltage
110 V
[110V] [120V][127V]
120 V
Default:[120V][127V]
127 V
High Efficiency mode
[Enabled] [Disabled]
Power the output from
Disabled
Enabled
Default: Disabled
Protected Bypass
Disabled
[Enabled] [Disabled]
Default: Enabled
Enabled
Overload prealarm
[10%] ... [102%]
Load % when overload
100
%
alarm occurs
Default: 100%
Redundancy
Level 0
Level 1
Set redunancy level
Default: 0
Level 2
Level 3
Level 4
Byp freq limit
Default disables
transfer to Bypass if the
measured bypass
4
Hz
frequency is below
the nominal 4%
Byp volt min limit
Default disables
transfer to Bypass if the
12
%
measured bypass voltage
level is below the nominal
output voltage minus 12%
Byp volt max limit
Default disables
transfer to Bypass if the
measured bypass voltage
12
%
level is above the nominal
output voltage plus 12%