Setting Of The Diagnostic Mode (Remote I/O) - Festo CPX-FB39 Description

Terminal cpx, bus node, network protocol sercos iii
Table of Contents

Advertisement

2
Installation
2.4.5

Setting of the diagnostic mode (remote I/O)

The diagnostic mode is available only in the remote I/O operating mode.
Diagnostic mode (remote I/O operating mode)
I/O diagnostics interface and status bits are switched off
I/O diagnostics interface is switched on
Status bits are switched on
Reserved
1) The I/O diagnostic interface occupies an additional 16 input and 16 output bits
2) The status bits occupy an additional 16 input bits
Tab. 2.3
Please Note
The diagnostics mode reduces the available address space.
• When planning your CPX terminal, consider that the number of input and output bits
available for communication is reduced with usage of the diagnostic mode.
Subsequent activation of the diagnostics mode requires a reconfiguration.
• Observe that the CPX-internal I/O image can be displaced during subsequent activa­
tion of the diagnostics mode.
• In this case, repeat the network configuration.
16
1)
2)
Setting DIL switch 2
2.1
2.2
(factory setting)
2.1
2.2
2.1
2.2
2.1
2.2
Festo – P.BE-CPX-FB39-EN – 1504NH – English
OFF
OFF
ON
OFF
OFF
ON
ON
ON