Festo CPX-FB39 Description page 56

Terminal cpx, bus node, network protocol sercos iii
Table of Contents

Advertisement

4
Diagnostics and error handling
SF (system failure) – system fault
LED (red)
Sequence
ON
OFF
LED flashes
ON
OFF
ON
OFF
ON
OFF
LED
not illuminated
1) The system fault LED flashes depending on the class of fault which has occurred.
Error class 1 (slight error): 1× flash, pause time
Error class 2 (error): 2× flashes, pause time
Error class 3 (severe error): 3× flashes, pause time
M (modify) – parameterisation modified or Force active
LED (yellow)
Process
ON
OFF
LED
illuminated
ON
OFF
LED flashes
ON
OFF
LED
not illuminated
1) The display of the Force function (LED flashing) has priority over the display of the setting for the system start (LED illuminated).
56
1)
Status
Simple error/information
(error class 1)
Error
(error class 2)
Serious error
(error class 3)
No error
Status
Setting: System start with
saved parametrisation and
saved CPX expansion;
Parameters and CPX
expansion are stored
permanently.
1)
Force is active
Setting: System start with
default parameterisation
(factory setting) and cur­
rent CPX expansion;
external parameterisation
is possible (presetting).
Significance/error handling
Description of error numbers in the
CPX system description
(è P.BE-CPX-SYS-...).
Significance / error handling
For replacement of the bus node or
CPX terminal in case of service,
parameterisation is not created
automatically by the higher-order
system (PLC/IPC).
• Save and apply the parameterisa­
tion when the bus node is re­
placed.
The Force function is enabled.
Further information can be found in
the CPX system description
(è P.BE-CPX-SYS-...).
Festo – P.BE-CPX-FB39-EN – 1504NH – English