Reaction to malfunctions in the control system

Festo P.BE-CDVI-DN-EN en 0805a
The reaction of the outputs to control or communication
malfunctions can be set by means of the parameters
"Fault Value" and "Fault Action"
"Idle Value" and "Idle Action"
The default setting is "Reset output".
Further information on parametrisation can be found in sec-
tion 2.2.6.
Note
Please observe the following if the outputs are reset in the
event of a PLC stop or field bus interruption or malfunc-
tion:
– Monostable valves move to normal position.
– Bistable valves remain in the current position.
– Mid-position valves move to the mid position (depending
on the valve type: pressurized, exhausted or blocked).