2. Startup
Festo P.BE-CDVI-DN-EN en 0805a
The valves of the CDVI-DN and the outputs of the modules in
the CP extension are set with separate parameters:
"Fault Action, Main Unit" parameter
You can use this parameter to define for each output whether
it is to freeze the current status in fault mode or assume a
certain output status (0/1).
Parameter
Meaning
value
0
The output is set to a certain output status (0 or 1).
The output status is defined with the parameter
"Fault Value, Main Unit".
1
The status of the output is frozen.
Tab. 2/2:
"Fault Value, Main Unit" parameter
You can use this parameter to define the output status
(0 or 1) which each output is to assume in fault mode.
Parameter
Meaning
value
0
Output is reset
1
Output is set
Tab. 2/3:
The set parameter value is only taken into account if the
relevant output is set to 0 in the Fault Action parameter.
2-21