"Fault Action, Main Unit Extension" parameter
The same function as above with "Main Unit," but for the out-
put module in the extension.
"Fault Value, Main Unit Extension" parameter
The same function as above with "Main Unit," but for the out-
put module in the extension.
Reaction of the outputs in idle mode
Idle mode is assumed by the stations when this is requested
by the master or scanner. In this status, the following applies:
Inputs are transmitted.
Outputs of the stations are no longer updated.
In idle mode, the outputs for valve control and for the output
module can assume one of the following statuses:
Reset output
Set output
Freeze current status of output
The status to be assumed can be determined separately for
each output. The default setting is "Reset output".
The valves of the CDVI-DN and the outputs of the modules in
the CP extension are set with separate parameters: