1. Installation
1-6
Removing
1. Switch off all power supplies (electric voltage,
compressed air).
2. Loosen each of the two mounting screws on the left-hand
end plate by approximately one turn.
3. Now unscrew the two mounting screws completely to
avoid twisting or squeezing the separator plate (seal).
4. Pull off the left end plate.
Mounting
1. Place the separator plate (seal) on the manifold block.
The separator plate must be fitted correctly on the guide
sleeves of the manifold block.
2. Position the left end plate too.
3. Tighten the two mounting screws alternately. Torque:
3.5 Nm (... 4 Nm)
Note
Make sure the separator plate (seal) is not squeezed on
one side as a result of uneven tightening of the cover
screws.
The requirements of the IP protection class cannot be
fulfilled if a seal is squeezed.
Festo P.BE-CDVI-DN-EN en 0805a