1. Installation
Festo P.BE-CDVI-DN-EN en 0805a
Warning
If the valve terminal is supplied with load voltage via an
output of a "safety I/O module", switch-on test pulses of
the "safety I/O module" may cause unexpected reactions
of the valve terminal.
Make sure any switch-on test pulses are reliably sup-
pressed or switched off.
Observe the following for the connection of the 24 V load
voltage (pin 2):
Observe the tolerance (21.6 V ... 26.4 V DC).
Check the 24 V load voltage of the valves while
the system is in operation.
Caution
Excessive voltages or short circuits can cause functional
damage on the CP..-SC-DN, whereby actuators can no
longer be controlled.
Protect the load voltage of the solenoid coils with
external fuses.
To ascertain the amperage of the fuses, first calculate
the maximum current consumption in accordance with
section 1.4.1.