Fieldbus Baud Rate And Fieldbus Length - Festo CDVI-DN Manual

Valve terminal with direct fieldbus connection, (type 15), devicenet
Hide thumbs Also See for CDVI-DN:
Table of Contents

Advertisement

1. Installation

1.3.2 Fieldbus baud rate and fieldbus length

Festo P.BE-CDVI-DN-EN en 0805a
The maximum permitted fieldbus length depends on the
baud rate used. Tab. 1/7 shows the reference values.
Baud rate
Maximum main
bus length
125 kBaud
500 m
250 kBaud
250 m
500 kBaud
100 m
Tab. 1/7: Maximum fieldbus and branch line lengths de-
pending on the baud rate (as per ODVA specifica-
tion V 2.0)
The maximum permitted length of a branch line depends on
the total length of the branch lines and on the baud rate.
Details can be found in the manuals for the your control sys-
tem or scanner.
Note
Refer to the manuals for your control system or bus
interface in order to ascertain which T-adapter and
maximum branch line length are permitted for your
controller.
Also take into account the sum of the branch line lengths
when calculating the maximum permitted length of the
fieldbus cable.
Information on setting the baud rate can be found in
section 1.2.2.
Branch line length
Maximum
Cumulative
156 m
6 m
78 m
39 m