1.3.2 Field bus baud rate and field bus length

1−14
The maximum permitted field bus length depends on the
baud rate used. Tab. 1/6 shows the nominal values.
Baud rate
Maximum main
b
bus length
l
125 kBaud
500 m
250 kBaud
250 m
500 kBaud
100 m
Tab. 1/6:
Maximum field bus and branch line lengths
depending on the baud rate (as per ODVA
specification V 2.0)
The maximum permitted length of a branch line depends on
the total length of the branch lines and on the baud rate.
Detailed specifications can be found in the manuals for the
your control system or scanner.
Please note
Refer to the manuals for your control system or bus in
·
terface in order to ascertain which T−adapter you should
use and the maximum branch line length which is per
mitted for your controller.
Take into account also the sum of the branch line lengths
·
when calculating the maximum permitted length of the
field bus cable.
Information on setting the baud rate can be found in
section 1.2.2.
Branch line length
th
maximum
6 m
6 m
Festo P.BE−CDVI−DN−EN en 0404NH
cumulative
156 m
78 m
39 m