194 en | System menus and dialogs
Element
Incoming Format
Errors
Incoming Retried
Messages
Total Outgoing
Messages
Outgoing Retried
Messages
Outgoing Failed
Messages
Auto scan
Stress test
Current Troubles
2018.03 | SE3v1.0 | DOC
Usage/Description
The number of messages received from this SE coordinator where
format error was detected. This field is yellow if 1.5% or more of
the messages had errors. A high level of message errors indicates a
serious communication problem.
The total number of messages successfully received from this SE
coordinator that indicated they were retried. This field is yellow if
1.5% or more of the messages are retried. A high level of retried
messages indicates a serious communication problem.
The total number of messages sent to this SE coordinator from the
Central Console.
The total number of message retries to this SE coordinator. This
field is yellow if 1.5% or more of the messages are retried. A high
level of retried messages indicates a serious communication
problem.
This is total number of messages that could not to be delivered to
this SE coordinator. This field is yellow if there are any failed
messages. Outgoing failed messages cause the Central Console to
display an alert message that communications have failed.
The auto scan function performs the above stress test proceeding
from one SE coordinator to the next after one of each type of map
is requested and received. After the last map type and before
proceeding to the next SE coordinator, a command is issued to
refresh the SE coordinator data so that when an auto scan
proceeds through all SE coordinators, all SE coordinators and
point troubles are updated. Auto scan is terminated by unselecting
the Auto scan checkbox or by closing the screen using the
[Cancel] button.
This checkbox causes the Central Console to continually request
maps from the SE coordinator. When in this mode, the Central
Console sends a new map request as soon as it receives a map
from the SE coordinator, rotating through the map types. This test
is used when diagnosing communications problems to create
artificially high traffic on the communication link without
interfering with the processing of alarms and tests. The stress test
ceases when the checkbox is cleared, or this screen is closed by
clicking the [Cancel] button.
This window displays all current troubles for this SE coordinator. In
the Current Transponder Status dialog, there is a low battery and
a tamper condition being reported for this SE coordinator. This
window also displays the restoration to a normal condition when it
occurs. When the fault is corrected, clicking the [Acknowledge]
button eliminates any restoration reports. Conditions, which were
not rectified, remain in the window.