MI 3152(H) EurotestXC (2,5 kV)
Testing RCDs
7.7
Various test and measurements are required for verification of RCD(s) in RCD protected
installations. Measurements are based on the EN 61557-6 standard.
The following measurements and tests (sub-functions) can be performed:
Contact voltage,
Trip-out time,
Trip-out current and
RCD Auto test.
Test parameters / limits
I ΔN
Rated RCD residual current sensitivity [10 mA, 30 mA, 100 mA, 300 mA, 500
mA, 1000 mA]
I ΔN/ I ΔNdc Rated RCD residual current sensitivity for special RCDs types
[30 mA / 6 mA d.c.]
Type
RCD type [AC, A, F, B*, B+*, EV RCD
Use
RCD / PRCD selection [fixed, PRCD, PRCD-S, PRCD-K, other]
Selectivity
Characteristic [G, S]
x IΔN
Multiplication factor for test current [0.5, 1, 2, 5]
Phase
Starting polarity [(+), (-), (+,-)]
Limit Uc
Conventional touch voltage limit [12 V, 25 V, 50 V]
Test
Test current shape [a.c., d.c.]
Test
Test [-, L/PE, L1/PE, L2/PE, L3/PE]
RCD
Refer to chapter 4.6.5.1 RCD standard for more information.
standard
Earthing
Refer to chapter 4.6.5 Settings for more information.
system
* Model MI 3152 only.
Figure 7.26: RCD menus