METREL EurotestXC MI 3152 Instruction Manual page 144

Eurotestxc eurotestxc 2,5 kv
Table of Contents

Advertisement

MI 3152(H) EurotestXC (2,5 kV)
Test procedure (MANUAL R, MANUAL I)
Enter the IMD function.
Set test parameter to MANUAL R or MANUAL I.
Set other test parameters / limits.
Connect test cable to the instrument.
Connect test leads to the object under test, see Figure 7.76.
Start the measurement.
Use the
alarms an insulation failure for L1.
Press
(If IMD switches off voltage supply, instrument automatically changes line
terminal selection to L2 and proceeds with the test when supply voltage is
detected.)
Use the
alarms an insulation failure for L2.
Press the
(If IMD switches off voltage supply, instrument automatically proceeds to the
PASS / FAIL / NO STATUS indication.)
Use
to select PASS / FAIL / NO STATUS indication.
Press
measurement.
Save results (optional).
Test procedure (AUTO R, AUTO I)
Enter the IMD function.
Set test parameter to AUTO R or AUTO I.
Set other test parameters / limits.
Connect test cable to the instrument.
Connect test leads to the object under test, see Figure 7.76.
Start the measurement.
Insulation resistance between L1-PE is decreased automatically according to limit
*)
value
every time interval selected with timer. To speed up the test press the
Press
(If IMD switches off voltage supply, instrument automatically changes line
terminal selection to L2 and proceeds with the test when supply voltage is
detected.)
or
keys to change insulation resistance
or the
key to change line terminal selection to L2.
or
keys to change insulation resistance
or the
key.
or the
key to confirm selection and complete the
or
keys until IMD alarms an insulation failure for L1.
or the
key to change line terminal selection to L2.
143
Tests and measurements
*)
until IMD
*)
until IMD