MI 3152(H) EurotestXC (2,5 kV)
Diagnostic test (MI 3152H only)
12.2
Uiso: 500V, 1000 V, 2500 V
DAR – Dielectric absorption ratio
Measuring range
0.01 ... 9.99
10.0 ... 100.0
PI – Polarization index
Measuring range
0.01 ... 9.99
10.0 ... 100.0
For Riso, R60, and Um sub-results technical specifications defined in chapter 12.1 R iso –
Insulation resistance apply.
R low – Resistance of earth connection and
12.3
equipotential bonding
Measuring range according to EN 61557 is 0.16 ... 1999 .
R – Resistance
Measuring range ()
0.00 ... 19.99
20.0 ... 199.9
200 ... 1999
R+, R – Resistance
Measuring range ()
0.0 ... 199.9
200 ... 1999
Open-circuit voltage ................................ 6.5 VDC ... 18 VDC
Measuring current ................................... min. 200 mA into load resistance of 2
Test lead compensation .......................... up to 5
The number of possible tests .................. > 1400, with a fully charged battery
Automatic polarity reversal of the test voltage.
Continuity – Continuous resistance measurement with
12.4
low current
R – Continuity resistance
Measuring range ()
0.0 ... 19.9
20 ... 1999
Open-circuit voltage ................................ 6.5 VDC ... 18 VDC
Short-circuit current ................................ max. 8.5 mA
Resolution
0.01
0.1
Resolution
0.01
0.1
Resolution ()
0.01
0.1
1
Resolution ()
0.1
1
Resolution ()
0.1
1
177
Technical specifications
Accuracy
(5 % of reading + 2 digits)
(5 % of reading)
Accuracy
(5 % of reading + 2 digits)
(5 % of reading)
Accuracy
(3 % of reading + 3 digits)
(5 % of reading)
Accuracy
(5 % of reading + 5 digits)
Accuracy
(5 % of reading + 10 digits)