Testing Of Insulation Monitoring Devices (Imd) - METREL EurotestIM Instruction Manual

Table of Contents

Advertisement

MI 3110 EurotestIM

5.4 Testing of insulation monitoring devices (IMD)

This function is intended for checking the alarm threshold of insulation monitor devices
(IMD) by applying a changeable resistance between L1/PE and L2/PE terminals.
See chapter 4.2 Function selection for instructions on
key functionality.
Test parameters for IMD test
Type [MANUAL R, MANUAL I, AUTO R, AUTO I]
MANUAL R: Minimum insulation resistance [OFF, 5 k ÷ 640 k]
MANUAL I: Maximum current [OFF, 0.1 mA ÷ 19.9 mA]
Limit
AUTO R: Minimum insulation resistance [OFF, 5 k ÷ 640 k], Timer
[1 s ÷ 99 s]
AUTO I: Maximum current [OFF, 0.1 mA ÷ 19.9 mA], Timer [1 s ÷ 99 s]
Test circuit for IMD test
Figure 5.16: Connection with 3-wire test lead
Measurements – a.c. LV IT installations
Figure 5.15: IMD test
32