Z Line M - High Precision Line Impedance And Prospective Short-Circuit Current - METREL EurotestXC MI 3152 Instruction Manual

Eurotestxc eurotestxc 2,5 kv
Table of Contents

Advertisement

MI 3152(H) EurotestXC (2,5 kV)
Z line m – High precision line impedance and
7.13
prospective short-circuit current
Measurement parameters / limits
Fuse Type
Selection of fuse type [Off, gG, NV, B, C, D, K, Custom]
Fuse I
Rated current of selected fuse
Fuse t
Maximum breaking time of selected fuse
1)
Test
Test [-, L/N, L/L, L1/N, L2/N, L3/N, L1/L2, L1/L3, L2/L3]
Ia(Ipsc)
Minimum short circuit current for selected fuse or custom value
1)
The measuring results (for phase – neutral or phase – phase line) are set according to
the setting. The parameter is meant for documentation.
Refer to Fuse tables guide for detailed information on fuse data.
Connection diagram
Figure 7.46: Phase-neutral or phase-phase high precision Line impedance measurement
Figure 7.45: Z line mΩ menu
– Connection of A 1143
122
Tests and measurements