MI 3152(H) EurotestXC (2,5 kV)
Measurement procedure
Enter the Z line m function.
Set test parameters / limits.
Connect test leads to A 1143 – Euro Z 290 A adapter and switch it on.
Connect A 1143 – Euro Z 290 A adapter to the instrument using RS232-PS/2 cable.
Connect test leads to the object under test, see Figure 7.46.
Start the measurement using
Save results (optional).
Figure 7.47: Examples of high precision Line impedance measurement result
Measurement results / sub-results
Z
Line impedance
Ipsc
Standard prospective short-circuit current
Imax
Maximal prospective short-circuit current
Imin
Minimal prospective short-circuit current
Imax2p
Maximal two-phases prospective short-circuit current
Imin2p
Minimal two-phases prospective short-circuit current
Imax3p
Maximal three-phases prospective short-circuit current
Imin3p
Minimal three-phases prospective short-circuit current
R
Resistance of line impedance
XL
Reactance of line impedance
Uln
Voltage L-N or L-L
Freq
Frequency
Standard prospective short-circuit current I
230 ��
��
=
������
��
400 ��
��
=
������
��
or
is calculated as follows:
PSC
��
= 230 �� ± 10 %
where
��−��
��
= 400 �� ± 10 %
where
��−��
123