MI 3152(H) EurotestXC (2,5 kV)
Modification of RCD Auto test procedure
RCD Auto test inserted steps
Re-activate RCD.
Test with 2I
, (+) positive polarity (new step 3).
N
Re-activate RCD.
Test with 2I
, (-) negative polarity (new step 4).
N
Inserted new Step 3
Figure A.3: Example of individual steps in RCD Auto test – Inserted 2 new steps
Test results / sub-results
t I∆N x1 (+)
Step 1 trip-out time (I
t I∆N x1 (-)
Step 2 trip-out time (I
t I∆N x2 (+)
Step 3 trip-out time (I
t I∆N x2 (-)
Step 4 trip-out time (I
t I∆N x5 (+)
Step 5 trip-out time (I
t I∆N x5 (-)
Step 6 trip-out time (I
t I∆N x0.5 (+)
Step 7 trip-out time (I
t I∆N x0.5 (-)
Step 8 trip-out time (I
I∆ (+)
Step 9 trip-out current ((+) positive polarity)
I∆ (-)
Step 10 trip-out current ((-) negative polarity)
I∆ d.c. (+)
Step 11 trip-out current ((+) positive polarity)
I∆ d,c, (-)
Step 12 trip-out current ((-) negative polarity)
Uc
Contact voltage for rated I
1)
Steps 11 and 12 are performed if parameter Use is set to 'other' and Type to EV RCD or
MI RCD.
A.3 Profile Finland (profile code ALAC)
Ia(Ipsc) limit modified in fuse types gG, NV, B, C, D and K.
Refer to Fuse tables guide for detailed information on fuse data.
=I
, (+) positive polarity)
N
=I
, (-) negative polarity)
N
=2I
, (+) positive polarity)
N
=2I
, (-) negative polarity)
N
=5I
, (+) positive polarity)
N
=5I
, (-) negative polarity)
N
=½I
, (+) positive polarity)
N
=½I
, (-) negative polarity)
N
N
194
Appendix B – Profile notes
Notes
RCD should trip-out
RCD should trip-out
Inserted new Step 4
1)
1)