RSTAT Redundancy Status Function Block

Description
The RSTAT label stands for Redundancy Status . This block is part of the Alarms/Monitors category.
Function
Used with redundant CPUs only, such as C70R. The output pins indicate the lead/reserve status of CPU A
and CPU B. The input can force a failover between CPUs.
Inputs
^FOVER – OFF-to-ON transition causes a manual failover between CPUs if a Reserve CPU is online and
available.
Outputs
A LEAD – ON when CPU A is the Lead, else OFF.
B LEAD – ON when CPU B is the Lead, else OFF.
A RSRV – ON when CPU A is the Reserve, else OFF.
B RSRV – ON when CPU B is the Reserve, else OFF.
Configurable Parameters
Properties Group
Block
Order
Revision 11
2/07

Table 96 Redundancy Status configuration parameters