Pick List Variable Tables; Table 3-19 Data From Drive Pick List Variables - Siemens SINAMICS PERFECT HARMONY GH180 Function Manual

Nxgpro communication medium-voltage variable frequency drive
Hide thumbs Also See for SINAMICS PERFECT HARMONY GH180:
Table of Contents

Advertisement

Modbus Communication
3.3 Parameter Assignment/Addressing
3.3.3

Pick List Variable Tables

Table 3-19
Data from Drive Pick List Variables
Name
None
Man Id
General Status
Motor Voltage
Total Current
Output Power
Motor Speed
Speed Demand
Speed Reference
Heartbeat
Drive State
Inp RMS Current
50
Manual ID Unit
Scaling
None
None
None
None
None
None
2001
None
None
2100
Volts
/1
2190
Amps
/1
2230
KW
/1
2014
%
/10
RPM
/1
Hz
/10
2060
%
/100
2010
%
/100
2220
None
None
2210
None
None
2130
Amps
/1
16 Bit Data
Notes
Type
None
None
None
Refer to Appendix
Bit Field
● Bit 0: Fault
● Bit 1: Alarm
● Bit 2: Running Forward
● Bit 3: Running Reverse
● Bit 4: Drive Ready
● Bit 5: Start/Stop Control From Network
● Bit 6: Speed Reference From Network
● Bit 7: At Speed Reference
● Bit 8: Speed In Percent
● Bit 9: Speed In RPM
● Bit 10: Speed In Hz
● Bit 11: Reserved for future use
● Bit 12: Reserved for future use
● Bit 13: Reserved for future use
● Bit 14: Reserved for future use
● Bit 15: Reserved for future use
Unsigned
Unsigned
Signed
Unsigned
Unsigned
Unsigned
Unsigned
1 count per millisecond
Unsigned
● 0 = Off
● 1 = Magnetizing
● 2 = Spinning Load
● 3 = Autotune
● 4 = Run
● 5 = Stop
● 6 = Coast
● 7 = Up Transfer
● 8 = Down Transfer
Unsigned
Function Manual, AB, A5E33486415A
Internal Drive Network
NXGpro Communication