Profibus Communication
6.2 Software Programming
● The PLC writes the contents of 'Net Input Flag 1', bit 9 (Network1Flag9_I) to create an input
medium voltage trip.
6.2.2

Programmable Outputs from the Drive

Description
There are 64 output bits available for user programming through the SOP file. These bits can
be programmed to set or reset any other bits used within the SOP.
Programming Procedure
1. Locate the first data from drive register that is programmable using Table
between Drive Parameter ID and Communication Protocol Address in Section Parameter
Assignment/Addressing .
You will see that the first programmable data from drive register for network 1 is register
'Data from Drive 03', which corresponds to parameter ID (9403).
2. Enter parameter ID (9403).
3. The pick list of data from drive variables will appear. Refer to Table
List Variables in Section Parameter Assignment/Addressing for a list of data from drive pick
list variables.
4. Scroll through the pick list until you come to 'Net1 Out Reg 1' and press [ENTER]. This
setting uses the first 16 bits of the possible 64 bits.
5. Select 'Net1 Out Reg 2' to use the second set of 16 bits, and so on.
The pick list variables and the corresponding programmable output bits are found in the
following tables for network 1 and 2, respectively.
Table 6-5
Pick list variable in 'Data from Drive Reg nn' menus Related Drctry.pro bits
Net1 Out Reg 1
Net1 Out Reg 2
Net1 Out Reg 3
Net1 Out Reg 4
Table 6-6
Pick list variable in 'Data from Drive Reg nn' menus Related Drctry.pro bits
Net2 Out Reg 1
Net2 Out Reg 2
Net2 Out Reg 3
Net2 Out Reg 4
142
Network 1: Programmable output bits (parameter ID 9403-9464)
Network 2: Programmable output bits (parameter ID 9503-9564)
Network1Flag0_O ~ Network1Flag15_O
Network1Flag16_O ~ Network1Flag31_O
Network1Flag32_O ~ Network1Flag47_O
Network1Flag48_O ~ Network1Flag63_O
Network2Flag0_O ~ Network2Flag15_O
Network2Flag16_O ~ Network2Flag31_O
Network2Flag32_O ~ Network2Flag47_O
Network2Flag48_O ~ Network2Flag63_O