Ethernet / IP Communication
5.5 Planning/Configuring
5.5.6

Network Interfaces

● The Anybus™ Ethernet/IP module uses a standard RJ-45 port located on the module to
support Network 1.
● The Anybus™ Ethernet/IP module uses a standard RJ-45 port located on the module to
support Network 2.
Multiple Drive LAN Ethernet Connection
To use the LAN connection to control one or more drives on an existing network complete the
following steps:
● Assign a unique IP address to each drive.
● Set the menu items of the TCP/IP Setup Menu (9300) for each drive.
● For Network 1, set the following menu items based on the settings unique to the network:
– IP Address (9960)
– Subnet Mask (9961)
– Gateway Address (9962)
● For Network 2, set the following menu items based on the settings unique to the network:
– IP Address (9336)
– Subnet Mask (9337)
– Gateway Address (9338)
Refer to Table
Assignment/Addressing of this chapter.
Figure 5-5
Ethernet I/P Communication Connection
The following hardware is required for this connection method:
● EtherFast 10/100 hub
● Ethernet Cat5 cable
5.5.7

PLC Setup using EDS files

An EDS file is a device description file in a specified format.
130
Network 2 Configure Parameters Menu (9916) in Section Parameter
NXGpro Communication
Function Manual, AB, A5E33486415A