Bit
Network1FixedRegBit7_I
Network1FixedRegBit8_I
Network1FixedRegBit9_I
Network1FixedRegBit10_I
Network1FixedRegBit11_I
Network1FixedRegBit12_I
Network1FixedRegBit13_I
Network1FixedRegBit14_I
Network1FixedRegBit15_I
Network1FixedRegBit3_I functions as a drive stop control bit only if parameter 'Start Stop Control'
1
(9945) is set to "Momentary". Otherwise this bit is reserved.
Note
To run the drive, the PLC must send 0x21 to register 'Data to Drive 01'. This hexadecimal value
sets bit 0 (run) and bit 5 (start/stop control from network).
To stop the drive, the PLC must send 0x08 or 0x00 to register 'Data to Drive 01'.
8.4.2

Fast Setup: Monitor drive status and speed feedback

To read status data from the drive, complete the following steps:
1. Set parameter 'Network 1 Type' (9901) to "DeviceNet".
2. Set parameter 'DeviceNet Baud Rate' (9905); this must match the baud rate of the PLC
controller.
3. Set parameter 'DeviceNet Address' (9908) to the desired network address for the drive.
4. Set parameter 'Velocity Units' (9080) to the desired motor speed units.
5. Refer to the Table
Protocol Address in Section Parameter Assignment/Addressing to obtain the addresses
for general status (Data from Drive 01) and motor speed feedback (Data from Drive 02)
from the drive.
NXGpro Communication
Function Manual, AB, A5E33486415A
Correspondence between Drive Parameter ID and Communication
DeviceNet (Profile 12) Communication
8.4 Planning/Configuring
Default Definition
Reserved for future assignment