To indicate the number of active faults:
1. The table shows that 'Data from Drive 04' is changeable, this can be set to indicate the
number of active faults.
2. Refer to Table
Address to determine that the corresponding parameter ID is 9404.
3. Enter parameter ID 9404.
4. The pick list of data from drive variables appears. As "number of active faults" is not an
option in the pick list, you must specify it manually.
5. Refer to Table
Addressing for a list of 'data from drive' pick list variables.
Since "number of active faults" is not a choice in the pick list, instead choose "Man Id"
(manual ID). The display shows "ManId-0000".
6. Refer to Appendix
determine its data ID number (3000).
7. Use arrow or number keys to enter 3000, and press [ENTER]. The display now shows
"ManId-3000".
The number of active faults will be sent to the PLC using register 'Data from Drive 04'.
● If the data ID number is not found, the error message "Invalid Id Entered" is displayed.
Ensure that the data ID is correct.
Table 9-22
Completed Settings for Given Example
PLC Address or Register
Data from Drive 01 (not changeable)
Data from Drive 02 (not changeable)
Data from Drive 03
Data from Drive 04
See also
Correspondence between Drive Parameter ID and Communication Protocol Address
(Page 224)
NXGpro Communication
Function Manual, AB, A5E33486415A
Correspondence between Drive Parameter ID and Communication Protocol
Data From Drive Pick List Variables in Section Parameter Assignment/
Output Data IDs and locate "number of active faults" in the tables to
Data
General status
Motor speed
Output power
Number of faults
ControlNet Communication
9.4 Planning/Configuring
Scaling
16 bits
RPM
kW
0 to 128