Network Status (Auto Detect) - Siemens SINAMICS PERFECT HARMONY GH180 Function Manual

Nxgpro communication medium-voltage variable frequency drive
Hide thumbs Also See for SINAMICS PERFECT HARMONY GH180:
Table of Contents

Advertisement

● Enter from a choice of variables in the pick lists. The pick lists in the menus contain the
most commonly used data variables. Refer to Section
for the pick lists.
Note
A pick list item can only be used once for each 'Data to Drive' register.
● For 'Data from Drive' registers, choose pick list option "Man Id" (manual ID) to manually
enter a variable that is not included in the pick lists, using the output data ID number. Use
the list of data IDs available in Appendix
corresponding ID number to enter the variable into the 'Data from Drive' register.
Note
The output data ID number is not the same as a parameter ID number.
See also
Correspondence between Drive Parameter ID and Communication Protocol Address
(Page 168)
Parameter Tables (Page 170)
Pick List Variable Tables (Page 173)
Output Data IDs (Page 277)
7.3.4

Network Status (auto detect)

An SOP flag is available to show the network status:
● For network 1: Network1CommOk_I
● For network 2: Network2CommOk_I
The SOP flag is set to "1" (true) when the network connection is operating normally, and "0"
(false) when it is not operating normally.
The network status is automatically detected. Detection time takes approximately 20-40
milliseconds.
If a longer network timeout is desired for a network that automatically detects the network
status, it must be implemented through SOP logic.
NXGpro Communication
Function Manual, AB, A5E33486415A
Parameter Assignment/Addressing
Output Data IDs to locate the variable and use the
ProfiDrive Communication
7.3 Planning/Configuring
187