Parameter Read/Write
E.3 Defining the PTD Registers
E.3

Defining the PTD Registers

The PTD registers are defined in the following table, which provides all possible contents of
the PTD registers. The PTD1 register can have a value of 0 to 127 for various commands as
described in the table.
Table E-2
Contents of PTD Registers 1 to 4
PTD Register
Register Function
PTD1: Bits 0 to 7 ID Command
Parameter Command
Pick List Command
Function Command
(refer to table below for
supported IDs)
Reserved
PTD1: Bits 8 to
Exponent
11
PTD2
Menu ID
306
Value
Description
0
No Operation
1
Read ID Type:
● 0 = Parameter
● 1 = Pick List Item
● 2 = Pick List with Manual ID (Manual ID Not Selected)
● 3 = Pick List with Manual ID (Manual ID Currently Selected)
● 4 = Function
2
Read Next ID
3
Read ID Minimum Value
4
Read ID Maximum Value
5
Read ID String Length
6 to 11
Read ID String (4 bytes per command)
12
Read ID Security Level (0, 5, 7)
13
Write ID Security Level (0, 5, 7)
14
Read ID Default Value
15
Read ID Default Used (0 = No, 1 = Yes)
16 to 20
Reserved for Future Use
21
Read Parameter Value
22
Write Parameter Value
23
Read Units Text Length
24
Read Units String (Bytes 1-40)
25
Read IP Address
26
Write IP Address
27 to 30
Reserved for Future Use
31
Read Pick List Item
32
Write Pick List Item (Not Using Drive ID)
33
Write Pick List Item (Using Drive ID)
34
Read Pick List Text Length
35 to 40
Read Pick List String (4 Bytes per Command)
41
Perform Function
42 to 47
Read Function String (4 Bytes per Command)
48 to 127
Reserved for Future Use
N/a
Exponent to be used for Write Parameter Value command
N/a
Menu ID for the required command
NXGpro Communication
Function Manual, AB, A5E33486415A