2.7
Safe Speed Monitor, SSM
The safety function SSM cannot be selected or deselected using external control signals.
SSM is active if all of the following conditions are met:
● You have enabled the safety function SSM with hysteresis.
● For the SSM function, you have set a monitoring velocity of > 0.
● The motor is switched on.
Principle of operation
● When the motor is switched on, the inverter compares the load speed with the velocity
Safety Integrated Function Manual, SINAMICS G120 and G120C
Function Manual, 01/2011, FW 4.4, A5E03052391B AB
limit (p9546 / p9346).
Figure 2-24
Time response and diagnostics of the safety function SSM (Safe Speed Monitor)
Description
2.7 Safe Speed Monitor, SSM
49