Installation Of Mc Power Supply Stepdown Transformer (Fr-Hcm2-H280K To H560K) - Mitsubishi Electric FR-HC2-7.5K Instruction Manual

Hide thumbs Also See for FR-HC2-7.5K:
Table of Contents

Advertisement

Installation of peripheral devices
(3) Environment
Avoid places where the equipment is subjected to oil mist, flammable gases, fluff, dust, dirt, etc.
Install the equipment in a clean place or protect it from suspended substances.
Do not place a flammable material near the equipment.
(4) Installation orientation
To prevent looseness, install the inrush current limit resistor (FR-HCR2) on a horizontal or vertical surface securely with
screws or bolts.
2.5.5

Installation of MC power supply stepdown transformer (FR-HCM2-H280K to H560K)

(1) Clearance
Because the MC power supply stepdown transformer generates heat, leave sufficient space around it.
(2) Installation place
Install the MC power supply stepdown transformer on nonflammable material. Direct installation on a flammable material
will cause a fire.
(3) Environment
Avoid places where the equipment is subjected to oil mist, flammable gases, fluff, dust, dirt, etc.
Install the equipment in a clean place or protect it from suspended substances.
(4) Installation orientation
To prevent looseness, install the MC power supply stepdown transformer on a horizontal or vertical surface securely with
screws or bolts.
NOTE
Since the charged section of the MC power supply stepdown transformer is uncovered, fully protect it to prevent
ground fault and electric shock.
26
10cm or more
10cm or more
10cm or more