Wiring of control circuit

2.13.3 Control circuit terminal layout

Dedicated board for FR-HC2
(1) Common terminals of the control circuit (SD, 5, SE, SE2)
 Terminals SD, 5, SE, and SE2 are all common terminals (0V) for I/O signals and are isolated from each other. Do not earth
(ground) these terminals.
Avoid connecting the terminal SD and 5 and the terminal SE and 5.
 Terminal SD is a common terminal for the contact input terminals (RES, SOF, X1, X2, ROH) and the pulse train output
terminal (FM). The open collector circuit is isolated from the internal control circuit by photocoupler.
 Terminal 5 is a common terminal for the analog output terminal AM. It should be protected from external noise using a
shielded or twisted cable.
 Terminal SE is a common terminal for the open collector output terminal (RDY, RSO, CVO, Y1, Y2). The contact input
circuit is isolated from the internal control circuit by photocoupler.
 Terminal SE2 is a common terminal for the open collector output terminal (Y3). The contact input circuit is isolated from the
internal control circuit by photocoupler.
 Do not connect anything to the free terminal (NC) of the control circuit.
Do not connect anything to the free terminal (NC) of the control circuit.
Using the terminal may cause a damage to the converter and the inverter.
62
5
IRL
NC
IRH
Y3
SE2
NC
88R 88S
A
NC
NC
NC
RDY
NC
NC
NC
NC
SE
CAUTION
TR1
TR2
IRO
MCO
RDO
RDI
Terminal screw size: M3
MCI
Terminals 5, IRH, IRL, TR1,
TR2, IRO, MCO, RDO, RDI,
and MCI are for manufacturer
setting. Keep them open.
B
C
NC AM
5
RSO
CVO
Y1
PC
PC
RES
SE
SE
Y2
PC
FM
Terminal screw size:
X1
X2
SOF
ROH
SD
SD
SD
M3.5