Description of parameters
[Special monitor selection No.]
Refer to page 86 for details of the monitor description.
Data
Description
H01 Input current
H02 Input voltage
H03 Bus voltage
H05 Power supply frequency
Electronic thermal relay
H06
load factor

Differ according to capacities. (55K or lower/75K or higher)

The regenerative status cannot be displayed. The regenerative status display is available only on the operation panel (FR-DU07-CNV).

Input terminal monitor details (when the terminal is ON: 1, when the terminal is OFF: 0, : undetermined value)
b15

Output terminal monitor details (when the terminal is ON: 1, when the terminal is OFF: 0, : undetermined value)
b15
[Fault data]
Refer to page 126 for details of fault description.
Data
Description
Data
No fault
H00
present
H11
E.OC2
H21
E.OV2
H30
E.THT
H40
E.FIN
H50
E.IPF
H51
E.UVT
H52
E.ILF
H90
E.OHT
HA3
E.OP3
[Converter status monitor]
Instruction
Item
Code
Converter
status
H7A
monitor
Converter
status
H79
monitor
(expansion)
 The signal within parentheses is in the initial status. Definitions change according to the Pr. 11 to Pr. 16 (output terminal function selection).
108
Increments
Data
0.01A/0.1A

H07 Input power
0.1V
0.1V
H08 Cumulative power
0.01Hz
Cumulative
H09
energization time
0.1%
RES
Description
Data
HB0
E.PE
HF6
HB1
E.PUE
HF7
HB2
E.RET
HF8
HB3
E.PE2
HF9
HC0
E.CPU
HFD
HC1
E.CTE
HC2
E.P24
HC4
E.CDO
HC5
E.IOH
HF2
E.2
HF3
E.3
Bit
Description
Length
b0 : RDY(Inverter run permission)
b1 : Power driving
b2 : Regenerative driving
b3 : RSO (converter reset)
8 bits
b4 : Y1 (overload)
b5 : Y2 (power supply phase
detecting)
b6 : CVO (converter running)
b7 : 88R (input contactor control)
b0 : RDY (Inverter run permission)
b1 : Power driving
b2 : Regenerative driving
b3 : RSO (converter reset)
b4 : Y1 (overload)
b5 : Y2 (power supply phase
detecting)
b6 : CVO (converter running)
16 bits
b7 : 88R (input contactor control)
b8 : ABC (fault)
b9 : 
b10 : 
b11 : 
b12 : 
b13 : 
b14 : 
b15 : Fault occurrence
Description
Increments
0.01kW/
0.1kW
1kWh
1h
SOF
ROH
88R
ABC
Fault record display example (instruction code H74)
Description
For read data H30B1
E.6
(Previous fault ...... THT)
E.7
(Latest fault ...... OPT)
E.8
E.9
E.13
[Example 1] HO2: Power driving
b15
0
0
H8100: Trip by a fault
b15
1
0
Data
Description
H0A Input power
*2

H0F Input terminal status
H10 Output terminal status
X2
X1
Y3
Y2
Y1
CVO
b15
0
0
1
1 0 0 0 0
Previous fault
(H30)
Example
[Example 1] HO2: Power driving
b7
0
0
0
0
0
0
1
[Example 2] H40: Converter running
b7
0
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
0
0
Increments
0.1kW/
1kW



b0
b0
RSO
RDY
b8b7
b0
1
0
1
1
0
0
0
1
Latest fault
(HB1)
b0
0
b0
0
b0
0
0
0
0
1
0
b0
0
0
0
0
0
0