Wiring of main circuit (FR-HC2-7.5K to 75K, FR-HC2-H7.5K to H220K)
(5) Wiring of high power factor converter and inverter
• These units should be connected to transmit commands from the high power factor converter to the inverter securely.
Connection method differs depending on the inverter series. Refer to the Instruction Manual of the inverter when
connecting.
Refer to the below table for the wiring length.
For the wire gauge of the main circuit terminals P/+ and N/- (across P and P, across N and N), refer to 2.6.3 Cable sizes of the
main control circuit terminals and earth (ground) terminals (refer to page 31).
Converter
(FR-HC2)
∗1
R4/
P/+
L14
S4/
N/-
L24
T4/
L34
RDY
Control
RSO
circuit
SE
Cable gauge for the
control circuit
<Wiring example of 7.5K>
88R 88S
A
B
NC
NC
NC
RDY
RSO
NC
NC
NC
NC
SE
SE
The terminal arrangement in the main circuit differs by capacity. Check the terminal arrangement on 2.6.2 Terminal arrangement of the main circuit terminal
(refer to page 28).
Across terminals P and P
Total wiring
Across terminals N and N
length
Other control signal lines
NOTE
 The converter operates as a common converter. Use terminals P/+ and N/- to connect it with the inverter. Do not
connect anything to the inverter power input terminals R/L1, S/L2, and T/L3. Incorrect connection to the inverter
power input will damage the inverter. Connecting opposite polarity of terminals P/+ and N/- will damage the inverter
and the converter.
 Do not connect the DC reactor to the inverter when using a high power factor converter.
38

Installation of a fuse is recommended to avoid the damage to spread in case of an
Inverter
inverter failure. Select a fuse according to the motor capacity. When using a motor, of
P/+
∗3
which the capacity is smaller than the inverter capacity by two ranks or more, select the
N/-
fuse with the capacity that is one rank lower than the inverter capacity. Refer to the fuse
selection table on page 11, 13.
When connecting several inverters, the wire gauge of terminal P/+ and N/- should be
∗2
X10
same as the wire gauge of the inverter's power supply side. (Refer to the Instruction
RES
Manual of the inverter.)
SD

The function of the inverter terminal, which is connected to the terminal RDY of the
converter, needs to be set at the inverter side.

Refer to the Instruction Manual of the inverter.
2
0.75 to 1.25mm
Do not insert MCCB between terminals P/+ and N/- (P and P, N and N).
Converter
R1/L11 S1/L21
N/-
P/+
88R 88S
A
B
C
NC AM
5
X1
X2
NC
NC
NC
RDY
RSO
CVO
Y1
PC
PC
RES
SOF
ROH
R4
S4/
R/L1 S/L2 T/L3
T4/
/L14
NC
NC
NC
NC
SE
SE
SE
Y2
PC
FM
SD
SD
SD
L24
L34
C
NC AM
5
X1
X2
CVO
Y1
PC
PC
RES
SOF
ROH
SE
Y2
PC
FM
SD
SD
SD
50m or less
30m or less
Inverter
N/-
P/+
A1
B1
C1
A2
B2
C2 10E 10
2
5
4
X10
RM
RH
RT
AU
STOP
MRS
RES
SD
FM
AM
1
SE
RUN
SU
IPF
OL
FU
SD
SD
STF
STR
JOG
CS
PC
A1
B1
C1
A2
B2
RM
RH
RT
AU
X10
SE
RUN
SU
IPF
OL
FU
C2 10E 10
2
5
4
STOP
MRS
RES
SD
FM
AM
1
SD
SD
STF
STR
JOG
CS
PC

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fr-hc2-h7.5kFr-hc2

Table of Contents