Connect the inverter control power supply directly to the power supply without connecting a converter in between.
MCCB
Power
supply
Cable gauge
0.75 to 2mm
NOTE
Refer to the Instruction Manual of the inverter, and remove the jumpers across terminals R/L1 and R1/L11 and across
terminals S/L2 and S1/L21 in the inverter main circuit.
Always connect the power supply to the inverter. It supplies power to the inverter's control power and large-capacity
cooling fan. If not connected, the inverter may come to a trip or be damaged.
(7) Wiring filter capacitor alarm detector and converter
Use the cable shown in the below table for the connection.
Cable gauge
Before wiring, read the Instruction Manual appended to the filter capacitor alarm detector carefully.
<Wiring example of 400K>
Reactor 1
(FR-HCL21-H400K)
R/
R2/
L12
L1
Power
S2/
S/
L2
L22
Supply
T/
T2/
L3
L32
R/L1
V1
AC410V
V2
AC430V
V3
S/L2
AC470V
Stepdown
transformer
(1PH 630VA)
<Wiring example of 560K>
Reactor 1
(FR-HCL21-H560K)
R2/
R/
L12
L1
Power
S2/
S/
Supply
L22
L2
T2/
T/
L3
L32
R/L1
V1
AC410V
V2
AC430V
V3
S/L2
AC470V
Stepdown
transformer
(1PH 630VA)
Connect the wiring to the terminals R5/L15 and S5/L25 of the MC power supply stepdown transformer by placing parallel with the wiring of (5) Wiring reactor
1 and converter (Refer to page 51).
Install the mini relay using the provided mini relay terminal block (PYF14T) and the mini relay clip (PYC-A1).