Wiring of main circuit (FR-HC2-H400K, H560K)
NOTE
• When connecting the converter to the inverter, match the control logic (sink logic (initial setting)/source logic). The
converter does not operate properly if the control logic is different.
(Refer to page 60 for the switching of the control logic. Refer to the Instruction Manual of the inverter for the switching
of the control logic of the inverter.)
• Keep the wiring length between terminals as short as possible.
• When sudden large distortion or depression of power supply occurs, reactor may generate abnormal acoustic noise.
This acoustic noise is caused by the power supply fault and not by the damage of the converter.
• Do not connect the DC reactor to the inverter when using a high power factor converter.
• When using a sine wave filter with FR-HC2 (75K or higher), select MT-BSL-HC as a reactor for the sine wave filter.
Check the connection order of the reactor 1 and the reactor 2. Incorrect connection may damage the
converter and reactors.
Always connect the terminal RDY of the converter to the terminal MRS or the inverter terminal of which X10
signal is assigned to. Also, always connect the terminal SE of the converter to the terminal SD of the inverter.
If these are not connected, the converter may be damaged.
2.9.2

Wiring of main circuit

(1) Wiring power supply and reactor 1
 Use the cable shown in the below table for the connection.
Model Name
Cable gauge (mm
FR-HCL21-H400K
FR-HCL21-H560K
 Use the moulded case circuit breaker (MCCB), the earth leakage circuit breaker (ELB) or the magnetic contactor shown in
the below table.
400K
MCCB
MC
Power
supply
Moulded Case Circuit Breaker (MCCB) or
Model Name
FR-HCL21-H400K
FR-HCL21-H560K
48
2
)
2 200
2 250
Reactor 1
(FR-HCL21-H400K)
R/
R2/
L12
L1
S/
S2/
L2
L22
T/
T2/
L3
L32
Earth Leakage Circuit Breaker (ELB)
(NF or NV type)
900A
1500A
CAUTION
560K
MCCB
MC
MC
Power
supply
MC
Magnetic Contactor (MC)
S-N800
S-N400 (3 in parallel)
Reactor 1
(FR-HCL21-H560K)
R/
R2/
L12
L1
S/
S2/
L2
L22
T/
T2/
L3
L32