Mitsubishi Electric FR-S520E Series Instruction Manual

Mitsubishi Electric FR-S520E Series Instruction Manual

Transistored inverter
Table of Contents

Advertisement

TRANSISTORIZED INVERTER
FR-S
500
INSTRUCTION MANUAL (Detailed)
SIMPLE INVERTER
FR-S520E-0.1K to 3.7K (-C)
FR-S540E-0.4K to 3.7K
FR-S520SE-0.1K to 1.5K
FR-S510WE-0.1K to 0.75K
WIRING
FUNCTIONS
PROTECTIVE
FUNCTIONS
SPECIFICATIONS
Chapter 1
Chapter 2
Chapter 3
Chapter 4

Advertisement

Table of Contents
loading

Summary of Contents for Mitsubishi Electric FR-S520E Series

  • Page 1 TRANSISTORIZED INVERTER FR-S INSTRUCTION MANUAL (Detailed) SIMPLE INVERTER FR-S520E-0.1K to 3.7K (-C) FR-S540E-0.4K to 3.7K FR-S520SE-0.1K to 1.5K FR-S510WE-0.1K to 0.75K Chapter 1 WIRING Chapter 2 FUNCTIONS PROTECTIVE Chapter 3 FUNCTIONS Chapter 4 SPECIFICATIONS...
  • Page 2 Thank you for choosing this Mitsubishi Transistorized inverter. This instruction manual (detailed) provides instructions for advanced use of the FR- S500 series inverters. Incorrect handling might cause an unexpected fault. Before using the inverter, always read this instruction manual and the instruction manual (basic) [IB-0600151E] packed with the product carefully to use the equipment to its optimum.
  • Page 3 2. Fire Prevention CAUTION Install the inverter and brake resistor on an incombustible wall without holes, etc. Installing the inverter and brake resistor directly on or near a combustible surface could lead to a fire. If the inverter has become faulty, switch off the inverter power. A continuous flow of large current could cause a fire.
  • Page 4 (2) Wiring CAUTION Do not fit capacitive equipment such as power factor correction capacitor, capacitor type filter (option FR-BIF(-H)) or surge suppressor to the output of the inverter. The connection orientation of the output cables U, V, W to the motor will affect the direction of rotation of the motor.
  • Page 5 CAUTION The electronic thermal relay function does not guarantee protection of the motor from overheating. Do not use a magnetic contactor on the inverter input for frequent starting/stopping of the inverter. Use a noise filter to reduce the effect of electromagnetic interference. Otherwise nearby electronic equipment may be affected.
  • Page 6: Table Of Contents

    CONTENTS 1. WIRING Standard connection diagram and terminal specifications ..2 1.1.1 Standard connection diagram ............... 2 1.1.2 Explanation of main circuit terminals............. 3 Main circuit terminals ...............6 1.2.1 Terminal block layout ..................6 1.2.2 Cables, wiring length, and crimping terminals..........8 1.2.3 Wiring instructions ..................
  • Page 7 1.5.3 Current input selection "AU signal": Pr. 60 to Pr. 63 setting "4"....38 1.5.4 Start self-holding selection (STOP signal): Pr. 60 to Pr. 63 setting "5" ..39 1.5.5 Output shut-off (MRS signal): Pr. 60 to Pr. 63 setting "6" ......39 1.5.6 External thermal relay input: Pr.
  • Page 8 2.3.14 Acceleration/deceleration pattern (Pr. 29 )..........88 2.3.15 Extended function display selection (Pr. 30 ) ..........89 2.3.16 Frequency jump (Pr. 31 to Pr. 36 ) ............. 89 2.3.17 Speed display (Pr. 37 )................90 2.3.18 Biases and gains of the frequency setting voltage (current) (Pr.
  • Page 9 2.11.2 Automatic torque boost selection (Pr. 98 )..........132 2.11.3 Motor primary resistance (Pr. 99 ) ............133 2.12 Maintenance function ............133 2.12.1 Maintenance output function (H1, H2 ) ............. 133 2.12.2 Current average value monitor signal (H3, H4, H5)....134 2.13 Brake parameters (FR-S520E-0.4K to 3.7K only) ....
  • Page 10 3.2.4 Acceleration/deceleration is not smooth............ 182 3.2.5 Motor current is large ................182 3.2.6 Speed does not increase................182 3.2.7 Speed varies during operation ..............182 3.2.8 Operation mode is not changed properly ..........183 3.2.9 Operation panel display is not operating ........... 183 3.2.10 Parameter write cannot be performed............
  • Page 11 1. WIRING This chapter explains the basic "wiring" for use of this product. Always read the instructions before use. For description of "installation", refer to the instruction manual (basic). 1.1 Standard connection diagram and terminal specifications ............. 1.2 Main circuit terminals ........1.3 How to use the control circuit terminals ..
  • Page 12: Standard Connection Diagram And Terminal Specifications

    Standard connection diagram and terminal specifications 1.1 Standard connection diagram and terminal specifications 1.1.1 Standard connection diagram Three-phase 200V power input Three-phase 400V power input Inverter MCCB MC Motor Three-phase AC R/L1 S/L2 power supply Earth T/L3 (Ground) External transistor common 24VDC power supply DC reactor Contact input common (source)
  • Page 13: Explanation Of Main Circuit Terminals

    Standard connection diagram and terminal specifications CAUTION To prevent a malfunction due to noise, keep the signal cables more than 10cm away from the power cables. Single-phase 200V power input Single-phase 100V power input MCCB Motor Power supply Earth (Ground) REMARKS •...
  • Page 14 Standard connection diagram and terminal specifications (2) Control circuit Symbol Terminal Name Definition When the STF and STR Turn on the STF signal to start Forward rotation signals are turned on forward rotation and turn it off start simultaneously, the stop to stop.
  • Page 15 Standard connection diagram and terminal specifications Symbol Terminal Name Definition Inputting 0 to 5VDC (or 0 to 10V) provides the maximum output Frequency setting frequency at 5V (10V) and makes input and output proportional. Switch between 5V and 10V using Pr. 73 "0-5V, 0-10V selection". (voltage signal) Input resistance 10kΩ.
  • Page 16: Main Circuit Terminals

    Main circuit terminals 1.2 Main circuit terminals 1.2.1 Terminal block layout 1) Three-phase 200V power input • FR-S520E-0.1K, 0.2K (-C) • FR-S520E-1.5K, 2.2K, 3.7K (-C) Jumper Jumper R/L1 S/L2 T/L3 R/L1 S/L2 T/L3 Power supply Motor Motor Power supply • FR-S520E-0.4K, 0.75K (-C) Jumper R/L1 S/L2...
  • Page 17 Main circuit terminals 3) Single-phase 200V power input • FR-S520SE-0.1K, 0.2K, 0.4K, 0.75K • FR-S520SE-1.5K Jumper Jumper R/L1 S/L2 R/L1 S/L2 Motor Power supply Motor Power supply 4) Single-phase 100V power input • FR-S510WE-0.1K, 0.2K, 0.4K • FR-S510WE-0.75K R/L1 S/L2 R/L1 S/L2 Motor Power supply...
  • Page 18: Cables, Wiring Length, And Crimping Terminals

    Main circuit terminals 1.2.2 Cables, wiring length, and crimping terminals The following table indicates a selection example for the wiring length of 20m. 1) Three-phase 200V power input Cable Size Ter- Tight- Crimping HIV cable PVC cable minal ening Applied Inverter Terminal Screw Torque...
  • Page 19: Wiring Instructions

    Main circuit terminals 1.2.3 Wiring instructions 1) Use crimping terminals with insulation sleeve to wire the power supply and motor. 2) Application of power to the output terminals (U, V, W) of the inverter will damage the inverter. Never perform such wiring. 3) After wiring, wire offcuts must not be left in the inverter.
  • Page 20: Selection Of Peripheral Devices

    Main circuit terminals 1.2.4 Selection of peripheral devices Check the inverter type of the inverter you purchased. Appropriate peripheral devices must be selected according to the capacity. Refer to the following list and prepare appropriate peripheral devices: 1) Three-phase 200V power input Moulded Case Circuit Breaker Magnetic...
  • Page 21 Main circuit terminals 3) Single-phase 200V power input Moulded Case AC Reactor DC Reactor Circuit Breaker Magnetic (*3) (*3) (MCCB *1, 4) or Contactor Motor FR-HAL- FR-HEL- Applied Inverter Earth Leakage (MC) Output FR-BAL- FR-BEL- Type (kW) Circuit Breaker (Refer to (Refer to page (Refer to page (ELB) (Refer to...
  • Page 22: Leakage Current And Installation Of Earth (Ground) Leakage Circuit Breaker

    Main circuit terminals 1.2.5 Leakage current and installation of earth (ground) leakage circuit breaker Due to static capacitances existing in the inverter I/O wiring and motor, leakage currents flow through them. Since their values depend on the static capacitances, carrier frequency, etc., take the following countermeasures. (1) To-earth (ground) leakage currents Leakage currents may flow not only into the inverter's own line but also into the other line through the earth (ground) cable, etc.
  • Page 23 Main circuit terminals (2) Line-to-line leakage currents Harmonics of Thermal relay MCCB leakage currents Motor flowing in static Power Inverter capacities between supply the inverter output Line static cables may operate capacitances the external thermal Line-to-Line Leakage Current Path relay unnecessarily. Countermeasures •...
  • Page 24 Main circuit terminals (3) Selecting the rated sensitivity current for the earth leakage circuit breaker When using the earth leakage circuit breaker with the inverter circuit, select its rated sensitivity current as follows, independently of the PWM carrier frequency: • Breaker for harmonic and surge Rated sensitivity current: Example of leakage...
  • Page 25 Main circuit terminals CAUTION •The earth (ground) leakage circuit breaker should be installed to the primary (power supply) side of the inverter. •In the connection neutral point earthed (grounded) system, the sensitivity current becomes worse for earth (ground) faults on the inverter secondary side.
  • Page 26: Power-Off And Magnetic Contactor (Mc)

    Main circuit terminals 1.2.6 Power-off and magnetic contactor (MC) (1) Inverter input side magnetic contactor (MC) On the inverter's input side, it is recommended to provide an MC for the following purposes. (Refer to page 10 for selection) 1) To release the inverter from the power supply when the inverter protective function is activated or the drive becomes faulty (e.g.
  • Page 27: Regarding The Installation Of The Reactor

    Main circuit terminals 1.2.7 Regarding the installation of the reactor When the inverter is installed near a large-capacity power transformer (500kVA or more with the wiring length of 10m or less) or the power capacitor is to be switched, an excessive peak current will flow in the power supply input circuit, damaging the converter circuit.
  • Page 28: Regarding Noise And The Installation Of A Noise Filter

    Main circuit terminals 1.2.8 Regarding noise and the installation of a noise filter Some noise enters the inverter causing it to malfunction and others are generated by the inverter causing the malfunction of peripheral devices. Though the inverter is designed to be insusceptible to noise, it handles low-level signals, so it requires the following general countermeasures to be taken.
  • Page 29: Earthing (Grounding) Precautions

    Main circuit terminals 1.2.9 Earthing (Grounding) precautions Leakage currents flow in the inverter. To prevent an electric shock, the inverter and motor must be earthed (grounded). Earthing (Grounding) must conform to the requirements of national and local safety regulations and electrical codes. (NEC section 250, IEC 536 class 1 and other applicable standards) Use the dedicated earth (ground) terminal to earth (ground) the inverter.
  • Page 30: Power Supply Harmonics

    Main circuit terminals 1.2.10 Power supply harmonics The inverter may generate power supply harmonics from its converter circuit to affect the power generator, power capacitor etc. Power supply harmonics are different from noise and leakage currents in source, frequency band and transmission path. Take the following countermeasure suppression techniques.
  • Page 31: Harmonic Suppression Guideline

    Main circuit terminals 1.2.11 Harmonic suppression guideline Harmonic currents flow from the inverter to a power receiving point via a power transformer. The harmonic suppression guideline was established to protect other consumers from these outgoing harmonic current. The three-phase 200V input specifications 3.7kW or less are previously covered by "Harmonic suppression guideline for household appliances and general-purpose products"...
  • Page 32 Main circuit terminals (1) Application of the guideline for specific consumers New installation/addition/ renewal of equipment Calculation of equivalent capacity sum Not more than reference capacity Sum of equivalent capacities Over reference capacity Calculation of outgoing harmonic current Is outgoing harmonic Over maximum value current equal to or lower than maximum value?
  • Page 33 Main circuit terminals Table 4 Harmonic Contents (Values of the fundamental current is 100%) Reactor 11th 13th 17th 19th 23rd 25th Not used Used (AC side) 14.5 Three-phase bridge Used (DC side) or (capacitor with filter pack smoothed) Used (AC, DC sides) ⎯...
  • Page 34 Main circuit terminals Table 5 Rated Capacities and Outgoing Harmonic Currents for Inverter Drive 6.6kV Outgoing Harmonic Current Converted from Rated Input Applied Equivalent of 6.6kV (mA) Current [A] rated Motor fundamental (without reactor, 100% operation ratio) capacity (kW) wave input (kVA) 200V 400V 11th 13th 17th 19th 23rd 25th...
  • Page 35: Inverter-Driven 400V Class Motor

    Main circuit terminals 1.2.12 Inverter-driven 400V class motor In the PWM type inverter, a surge voltage attributable to wiring constants is generated at the motor terminals. Especially for a 400V class motor, the surge voltage may deteriorate the insulation. When the 400V class motor is driven by the inverter, consider the following measures: •Measures It is recommended to take either of the following measures:...
  • Page 36: How To Use The Control Circuit Terminals

    How to use the control circuit terminals 1.3 How to use the control circuit terminals 1.3.1 Terminal block layout In the control circuit of the inverter, the terminals are arranged as shown below: Terminal arrangement of control circuit PC SE SD SD STF RM RH Terminal screw size: M2...
  • Page 37: Changing The Control Logic

    How to use the control circuit terminals 1.3.3 Changing the control logic The input signals are set to sink logic. To change the control logic, the jumper connector under the setting dial must be moved to the other position. Change the jumper connector position using tweezers, a pair of long-nose pliers etc.
  • Page 38 How to use the control circuit terminals 2) Source logic type • In this logic, a signal switches on when a current flows into the corresponding signal input terminal. Terminal PC is common to the contact input signals. For the open collector output signals, terminal SE is a positive external power supply terminal.
  • Page 39: Input Terminals

    Input terminals 1.4 Input terminals 1.4.1 Run (start) and stop (STF, STR, STOP) To start and stop the motor, first switch on the input power supply of the inverter to turn on the magnetic contactor at the operation-ready when there is a magnetic contactor on the input side, then start the motor with the forward or reverse rotation start signal.
  • Page 40 Input terminals DC Injection Brake and Coasting to Stop Functionality External Operation or Combined PU Operation or Combined Operation Operation Operation Pr. 79 = "0", "2", "3" Pr. 79 = "0", "1", "4" Mode Terminals STF (STR)-SD Set frequency Set frequency Stop key DC Injection disconnected...
  • Page 41 Input terminals REMARKS *1. The "starting frequency" in Pr. 13 (factory-set to 0.5Hz) may be set between 0 and 60Hz. *2. If the next start signal is given during DC injection brake operation, the DC injection brake is disabled and restart is made. *3.
  • Page 42: Connection Of Frequency Setting Potentiometer And Output Frequency Meter (10, 2, 5, 4, Au)

    Input terminals 1.4.2 Connection of frequency setting potentiometer and output frequency meter (10, 2, 5, 4, AU) The analog frequency setting input signals that may be entered are voltage and current signals. For the relationships between the frequency setting input voltages (currents) and output frequencies, refer to the following diagram.
  • Page 43: External Frequency Selection (Rex, Rh, Rm, Rl)

    Input terminals (2) Current input (4, 5, AU) To automatically perform operation under constant pressure or temperature control using a fan, pump etc., enter the controller output signal of 4 to 20mADC across terminals 4-5. Terminals AU-SD must be shorted to use the 4 to 20mADC signal for operation. (Assign the signal AU using any of Pr.
  • Page 44 Input terminals Multi-Speed Setting Terminal Input Set Frequency REX- Speed Parameter Remarks Range Speed 1 ⎯⎯⎯⎯⎯⎯⎯ (high OFF OFF Pr. 4 0 to 120Hz speed) Speed 2 ⎯⎯⎯⎯⎯⎯⎯ (middle OFF OFF Pr. 5 0 to 120Hz speed) Speed 3 ⎯⎯⎯⎯⎯⎯⎯ (low OFF OFF OFF Pr.
  • Page 45: Indicator Connection And Adjustment (Fm)

    Input terminals 1.4.4 Indicator connection and adjustment (FM) The output frequency, etc. of the inverter can be indicated by a DC ammeter of 1mA full-scale deflection and maximum 300Ω internal resistance or a commercially available digital indicator which is connected across terminals FM-SD. The indicator can be calibrated from the operation panel or parameter unit.
  • Page 46 Input terminals Output waveform of terminal FM The output signal of terminal FM has a pulse waveform as shown in the table below and the number of its pulses is proportional to the inverter output frequency. The output voltage (average voltage) is also proportional to the output frequency. Terminal FM Output Voltage Specifications Inverter...
  • Page 47: Control Circuit Common Terminals (Sd, 5, Se)

    Input terminals • Digital indicator Since the digital indicator counts and displays the number of pulses, adjust it from the operation panel or parameter unit. The inverter output, at which the reference pulses of 1440 pulses/s are output, can be set in Pr. 55 when frequency monitoring is used as reference, or in Pr. 56 when current monitoring is used as reference.
  • Page 48: How To Use The Input Signals (Assigned Terminals Rl, Rm, Rh, Str)

    How to use the input signals (assigned terminals RL, RM, RH, STR) 1.5 How to use the input signals (assigned terminals RL, RM, RH, STR) These terminals can be Pr. 60 "RL terminal function selection" changed in function by Pr. 61 "RM terminal function selection" Page 108 setting Pr.
  • Page 49: Start Self-Holding Selection (Stop Signal): Pr. 60 To Pr. 63 Setting "5

    How to use the input signals (assigned terminals RL, RM, RH, STR) 1.5.4 Start self-holding selection (STOP signal): Pr. 60 to Pr. 63 "5" setting This connection example is used when you want to self-hold the start signal (forward rotation, STOP reverse rotation).
  • Page 50: External Thermal Relay Input: Pr. 60 To Pr. 63 Setting "7

    How to use the input signals (assigned terminals RL, RM, RH, STR) 1.5.6 External thermal relay input: "7" Pr. 60 to Pr. 63 setting When the external thermal relay or built-in thermal relay Thermal relay of the motor (thermal relay protector,etc.) is actuated to Inverter Motor protect the motor from overheating, the inverter output...
  • Page 51: Reset Signal: Pr. 60 To Pr. 63 Setting "10

    How to use the input signals (assigned terminals RL, RM, RH, STR) 1.5.8 Reset signal: "10" Pr. 60 to Pr. 63 setting Used to reset the alarm stop state established when the inverter's protective function is activated. The reset signal immediately sets the control circuit to the initial (cold) status, e.g.
  • Page 52: Pid Control Valid Terminal: Pr. 60 To Pr. 63 Setting "14

    How to use the input signals (assigned terminals RL, RM, RH, STR) 1.5.9 PID control valid terminal: "14" Pr. 60 to Pr. 63 setting To exercise PID control, turn on the X14 signal. When this signal is off, ordinary inverter operation is performed. For more information, refer to page 123. ♦...
  • Page 53: Connection To The Stand-Alone Option

    Connection to the stand-alone option 1.6 Connection to the stand-alone option The inverter accepts a variety of stand-alone option units as required. Incorrect connection will cause inverter damage or accident. Connect and operate the option unit carefully in accordance with the corresponding option unit manual. 1.6.1 Connection of the dedicated external brake resistor (option) (FR-S520E-0.4K to 3.7K only)
  • Page 54: Connection Of The Brake Unit (Bu Type)

    Connection to the stand-alone option 1.6.2 Connection of the brake unit (BU type) Connect the BU type brake unit correctly as shown below. Incorrect connection will damage the inverter. Remove jumpers across terminals HB-PC and TB-HC and connect a jumper across terminals PC-TB of the brake unit. Inverter MCCB Motor...
  • Page 55: Connection Of The High Power Factor Converter (Fr-Hc)

    Connection to the stand-alone option 1.6.3 Connection of the high power factor converter (FR-HC) When connecting the high power factor converter (FR-HC) to suppress power supply harmonics, perform wiring securely as shown below. Incorrect connection will damage the high power factor converter and inverter. High power factor converter (FR-HC) (Caution 3) Inverter...
  • Page 56: Connection Of The Power Regeneration Common Converter (Fr-Cv)

    Connection to the stand-alone option 1.6.4 Connection of the power regeneration common converter (FR-CV) When connecting the FR-CV type power regeneration common converter, connect the inverter terminals (P, N) and FR-CV type power regeneration common converter terminals as shown below so that their signals match with each other. (Caution 2) Dedicated stand-alone FR-CV power regeneration...
  • Page 57: Handling Of The Rs-485 Connector

    Handling of the RS-485 connector 1.7 Handling of the RS-485 connector <RS-485 connector pin layout> View A of the inverter (receptacle View A side) 1) SG 5) SDA 2) P5S 6) RDB 3) RDA 7) SG 8) to 1) 4) SDB 8) P5S View A CAUTION...
  • Page 58: Wiring Of Rs-485 Communication

    Example of product available on the market (as of September, 2006) Model Maker Mitsubishi Electric Engineering Co., Ltd. FA-T-RS40 *The converter cable cannot connect two or more inverters (the computer and inverter are connected on a 1:1 basis). Since the product is packed with the RS- 232C cable and RS-485 cable (10BASE-T + RJ-45 connector), the cable and connector need not be prepared separately.
  • Page 59 Handling of the RS-485 connector (2) Combination of computer and multiple inverters (1:n connection) Station n Station 0 Station 1 (Max. 32 inverters) Computer Inverter Inverter Inverter RS-485 RS-485 RS-485 connector connector connector RS-485 interface/ Distribution terminal terminal Terminating resistor 10BASE-T cable 1) RJ-45 connector 2) Station 1...
  • Page 60 Handling of the RS-485 connector <Wiring methods> 1) Wiring of one RS-485 computer and one inverter Computer Side Terminals Inverter Signal Cable connection and signal direction Description name RS-485 connector 10 BASE-T Cable Receive data Receive data Send data Send data Request to send Request to send (*1)
  • Page 61: Design Information

    Design information 1.8 Design information 1) Provide electrical and mechanical interlocks for MC1 and MC2 which are used for bypass operation. When the wiring is incorrect and if there is a bypass operation circuit as shown below, the inverter will be damaged by leakage current from the power supply due to arcs generated at the time of switch-over or chattering caused by a sequence error.
  • Page 62: Failsafe Of The System Which Uses The Inverter

    Failsafe of the system which uses the inverter 1.9 Failsafe of the system which uses the inverter When a fault occurs, the inverter trips to output an alarm. However, an alarm output signal may not be output at an inverter alarm occurrence when the detection circuit or output circuit fails, etc.
  • Page 63 Failsafe of the system which uses the inverter 2) Checking the inverter operating status Power inverter operation ready supply completion signal Operation ready signal (RY signal) is output when the inverter power is on DC injection brake operation point and the inverter becomes operative. DC injection brake operation Check if the RY signal is output after...
  • Page 64 Failsafe of the system which uses the inverter (2) Backup method outside the inverter Even if the interlock is provided by the inverter status signal, enough failsafe is not ensured depending on the failure status of the inverter itself. For example, even if the interlock is provided using the inverter alarm output signal, start signal and RUN signal output, there is a case where an alarm output signal is not output and RUN signal is kept output even if an inverter alarm occurs.
  • Page 65: Functions

    2. FUNCTIONS This chapter explains the "functions" for use of this product. For simple variable-speed operation of the inverter, the factory settings of the parameters may be used as they are. Set the necessary parameters to meet the load and operational specifications. Refer to the instruction manual (basic) for the operation procedures.
  • Page 66: Function (Parameter) List

    Function (Parameter) list 2.1 Function (Parameter) list CAUTION indicates that the setting can be changed during operation if Pr. 77 "parameter write disable selection" has been set to "0" (factory setting). (Note that the Pr. 53, Pr. 70 and Pr. 72 values can be changed only during PU operation.) Minimum Cus- Indica-...
  • Page 67 Function (Parameter) list The extended function parameters are made valid by setting "1" in Pr. 30 "extended function display selection". (For more detailed information on the way to set Pr. 30, refer to the instruction manual (basic).) Cus- Minimum Func- Para- Indica- Factory...
  • Page 68 Function (Parameter) list Cus- Minimum Func- Para- Indica- Factory Refer Name Setting Range Setting tomer tion meter tion Setting Increments Setting Multi-speed setting 0 to 120Hz, - - - 0.1Hz - - - (speed 4) Multi-speed setting 0 to 120Hz, - - - 0.1Hz - - - (speed 5)
  • Page 69 Function (Parameter) list Cus- Minimum Func- Para- Indica- Factory Refer Name Setting Range Setting tomer tion meter tion Setting Increments Setting Up-to- frequency 0 to 100% sensitivity Output frequency 0 to 120Hz 0.1Hz detection Output frequency detection for 0 to 120Hz, - - - 0.1Hz - - - reverse...
  • Page 70 Function (Parameter) list Cus- Minimum Func- Para- Indica- Factory Refer Name Setting Range Setting tomer tion meter tion Setting Increments Setting 0: Output frequency, 1: Output current, Operation 100:Set frequency panel display during stop/output data selection frequency during operation 0: Setting dial Frequency frequency setting setting...
  • Page 71 Function (Parameter) list Cus- Minimum Func- Para- Indica- Factory Refer Name Setting Range Setting tomer tion meter tion Setting Increments Setting RL terminal function 0: RL, 1: RM, 2: RH, selection 3: RT, 4: AU, 5: STOP, RM terminal 6: MRS, 7: OH, function 8: REX, 9: JOG, selection...
  • Page 72 Function (Parameter) list Cus- Minimum Func- Para- Indica- Factory Refer Name Setting Range Setting tomer tion meter tion Setting Increments Setting Soft- Long wiring mode Soft-PWM Absence Absence setting 1 Presence Absence 10 Absence Presence 11 Presence Presence 0, 100: Thermal characteristic for Mitsubishi standard motor...
  • Page 73 Function (Parameter) list Cus- Minimum Func- Para- Indica- Factory Refer Name Setting Range Setting tomer tion meter tion Setting Increments Setting 0: Reset normally enabled/PU stop key disabled 1: Enabled at alarm occurrence only/PU Reset stop key disabled selection/PU 14: Reset normally enabled/normally stop selection decelerated to stop...
  • Page 74 Function (Parameter) list Cus- Minimum Func- Para- Indica- Factory Refer Name Setting Range Setting tomer tion meter tion Setting Increments Setting Multi-speed setting 0 to 120Hz, - - - 0.1Hz - - - (speed 12) Multi-speed setting 0 to 120Hz, - - - 0.1Hz - - - (speed 13)
  • Page 75 Function (Parameter) list Additional parameters Minimum Cus- Func- Parame- Indi- Setting Factory Refer Name Setting Range tomer tion ters cation Incre- Setting Setting ments Maintenance H1 (503) 0 to 999 timer (1000h) Maintenance H2 (504) timer alarm output 0 to 999, - - - (1000h) (36000h) set time...
  • Page 76 Function (Parameter) list Communication Parameters Minimum Cus- Func Parame- Indica- Setting Factory Refer Name Setting Range tomer tion tion Incre- Setting Setting ments 0 to 31: Specify Communication the station n1 (331) station number number of the inverter. 48: 4800bps, Communication n2 (332) 96: 9600bps,...
  • Page 77 Function (Parameter) list PU parameters When the parameter unit (FR-PU04) is used, operation from the operation panel is not accepted. (The stop key ( STOP ) is valid) RESET Minimum Cus- Func Parame- Indica- Setting Factory Refer Name Setting Range tomer tion tion...
  • Page 78 Function (Parameter) list Calibration parameters Minimum Cus- Func- Parame- Indi- Setting Factory Refer Name Setting Range tomer tion ters cation Incre- Setting Setting ments FM terminal ⎯⎯ ⎯⎯ ⎯⎯ C1 (900) calibration Frequency C2 (902) setting voltage 0 to 60Hz 0.1Hz bias frequency Frequency setting...
  • Page 79: List Of Parameters Classified By Purpose Of Use

    List of parameters classified by purpose of use 2.2 List of parameters classified by purpose of use Set the parameters according to the operating conditions. The following list indicates purpose of use and corresponding parameters. Parameter Numbers Purpose of Use Parameter numbers which must be set Use of extended function parameters Pr.
  • Page 80 List of parameters classified by purpose of use Parameter Numbers Purpose of Use Parameter numbers which must be set Pr. 54, Pr. 55, Pr. 56, Frequency meter calibration calibration parameter C1 Display of monitor on operation panel or Pr. 52, communication parameter n16 parameter unit (FR-PU04) Display of speed, etc.
  • Page 81: Explanation Of Functions (Parameters)

    Explanation of functions (parameters) 2.3 Explanation of functions (parameters) 2.3.1 Torque boost (Pr. 0 , Pr. 46 Increase the setting value when the distance between the inverter and motor is long or when the motor torque in the low speed range is insufficient (when stall prevention is activated), etc.
  • Page 82: Maximum And Minimum Frequency (Pr. 1 , Pr. 2 )

    Explanation of functions (parameters) 2.3.2 Maximum and minimum frequency (Pr. 1 , Pr. 2 You can clamp the upper and lower limits of the output frequency. Output frequency (Hz) Pr.1 Set frequency Pr.2 5,10V (4mA) (20mA) Parameter Name Factory Setting Setting Range Maximum frequency 60Hz...
  • Page 83: Base Frequency, Base Frequency Voltage (Pr.3 , Pr.19 , Pr.47 )

    Explanation of functions (parameters) 2.3.3 Base frequency, base frequency voltage (Pr.3 , Pr.19 , Pr.47 Used to adjust the inverter outputs (voltage, frequency) to the motor rating. Pr.19 Output frequency (Hz) Pr.3 Pr.47 Factory Setting Parameter Name Remarks Setting Range ⎯⎯...
  • Page 84 Explanation of functions (parameters) CAUTION 1. Set 60Hz in Pr. 3 "base frequency" when using a Mitsubishi constant-torque motor. 2. When automatic torque boost is selected, Pr. 47 is invalid. When automatic torque boost is selected, setting "- - -" or "888" in Pr. 19 uses the rated output voltage.
  • Page 85 Explanation of functions (parameters) 2.3.4 Multi-speed operation (Pr. 4 , Pr. 5 , Pr. 6 Pr. 24 to Pr. 27 , Pr. 80 to Pr. 87 Used to switch between the predetermined running speeds. Any speed can be selected by merely switching on/off the corresponding contact signals (RH, RM, RL, REX signals).
  • Page 86: Acceleration/Deceleration Time (Pr. 7 , Pr. 8 , Pr. 20 , Pr. 44 , Pr. 45 )

    Explanation of functions (parameters) CAUTION 1. The multi-speed settings override the main speeds (across terminals 2-5, 4- 5, setting dial). When the multi-speed settings and setting dial are used in the combined operation mode (Pr. 79 = 3), the multi-speed settings have precedence.
  • Page 87 Explanation of functions (parameters) <Setting> •Use Pr. 7 and Pr. 44 to set the acceleration time required to reach the frequency set in Pr. 20 from 0Hz. •Use Pr. 8 and Pr. 45 to set the deceleration time required to reach 0Hz from the frequency set in Pr.
  • Page 88: Selection And Protection Of A Motor (Pr. 9 , Pr. 71 , H7 )

    Explanation of functions (parameters) 2.3.6 Selection and protection of a motor (Pr. 9 , Pr. 71 , H7 Set the motor used and protect the motor from overheat. This feature provides the optimum protective characteristics, including reduced motor cooling capability, at low speed. POINT •When using the Mitsubishi constant-torque motor Set "1"...
  • Page 89 Explanation of functions (parameters) REMARKS •When running two motors with one inverter, you can set the electronic thermal relay function of each inverter. First Motor Electronic Thermal Relay Second Motor Electronic Thermal Pr. 71 Function Relay Function applied additional Pr. 9 RT = OFF RT = ON parameter...
  • Page 90: Dc Injection Brake (Pr. 10 , Pr. 11 , Pr. 12 )

    Explanation of functions (parameters) 2.3.7 DC injection brake (Pr. 10 , Pr. 11 , Pr. 12 By setting the DC injection brake voltage (torque) at a stop, operation time, and operation starting frequency, the timing of applying the DC injection brake Pr.10 to stop the braking torque the "Operation...
  • Page 91: Starting Frequency (Pr. 13 )

    Explanation of functions (parameters) 2.3.8 Starting frequency (Pr. 13 The starting frequency at Output frequency which the start signal is (Hz) turned on can be set in the range 0 to 60Hz. Frequency which is output by the inverter first at a start Pr.13 and gives great influence to Time...
  • Page 92: Load Pattern Selection (Pr. 14 )

    Explanation of functions (parameters) 2.3.9 Load pattern selection (Pr. 14 You can select the optimum output characteristic (V/F characteristic) for the application and load characteristics. Pr.14 = 1 Pr.14 = 2 Pr.14 = 0 Pr.14 = 3 For constant-torque For reduced-torque For lift For lift loads...
  • Page 93: Jog Operation (Pr.15 , Pr.16 )

    Explanation of functions (parameters) 2.3.10 Jog operation (Pr.15 , Pr.16 To start/stop jog operation in the external operation mode, choose the Output frequency (Hz) jog operation function in input terminal Pr.20 function selection, turn on the jog Jog frequency Forward signal, and turn on/off the start signal rotation setting range...
  • Page 94: Stall Prevention Function And Current Limit Function (Pr. 21 )

    Explanation of functions (parameters) 2.3.12 Stall prevention function and current limit function (Pr. 21 You can make setting to prevent stall caused by overcurrent and/or to prevent the inverter from resulting in an overcurrent trip (to disable fast-response current limit that limits the current) when an excessive current flows due to sudden load fluctuation or ON-OFF on the output side of a running inverter.
  • Page 95 Explanation of functions (parameters) CAUTION •If the load is heavy or the acceleration/deceleration time is short, the stall prevention may be activated and the motor not stopped in the preset acceleration/deceleration time. Therefore, set optimum values to the Pr. 21 and stall prevention operation level.
  • Page 96: Stall Prevention (Pr. 22 , Pr. 23 , Pr. 28 )

    Explanation of functions (parameters) 2.3.13 Stall prevention (Pr. 22 , Pr. 23 , Pr. 28 Set the output current level (% value to the rated inverter output current) at which the output frequency will be adjusted to prevent the inverter from stopping due to overcurrent etc.
  • Page 97 Explanation of functions (parameters) REMARKS When the fast-response current limit is set in Pr. 21 "stall prevention function selection" (factory setting), do not set any value above 170% in Pr. 22. The torque will not be developed by doing so. If the Pr.
  • Page 98: Acceleration/Deceleration Pattern (Pr. 29 )

    Explanation of functions (parameters) 2.3.14 Acceleration/deceleration pattern (Pr. 29 Set the acceleration/deceleration pattern. Set value 0 Set value 1 Set value 2 [Linear [S-pattern [S-pattern acceleration/deceleration] acceleration/deceleration A] acceleration/deceleration B] Time Time Time Factory Setting Parameter Name Remarks Setting Range Acceleration/ 0, 1, 2 Setting is enabled when Pr.
  • Page 99: Extended Function Display Selection (Pr. 30 )

    Explanation of functions (parameters) 2.3.15 Extended function display selection (Pr. 30 Used to display the extended function parameters. Refer to page 56 for the extended function parameter list. Refer to the instruction manual (basic) for the parameter setting method. Factory Setting Parameter Name...
  • Page 100: Speed Display (Pr. 37 )

    Explanation of functions (parameters) 2.3.17 Speed display (Pr. 37 You can change the output frequency indication or set frequency of the operation panel and parameter unit (FR-PU04) to the motor speed or machine speed. Factory Setting Parameter Name Remarks Setting Range 0:Output Setting is enabled...
  • Page 101: Biases And Gains Of The Frequency Setting Voltage (Current)

    Explanation of functions (parameters) 2.3.18 Biases and gains of the frequency setting voltage (current) (Pr. 38 , Pr. 39 , C2 to C7 You can set the magnitude (slope) of the output frequency as desired in relation to the external frequency setting signal (0 to 5V, 0 to 10V or 4 to 20mADC). The "bias"...
  • Page 102 Explanation of functions (parameters) <Setting> (1) How to change the highest frequency (2) Adjusting the deviation of the highest frequency from the Pr. 38 (Pr. 39) setting. (2)-1) Make adjustment with a voltage applied directly across terminals 2-5 (with a current flowing across terminals 4-5) (2)-2) Make adjustment at any point without a voltage applied across terminals 2-5 (without a current flowing across terminals 4-5)
  • Page 103 Explanation of functions (parameters) Changing example Changing the calibration parameter C4 "frequency setting voltage gain" value POINT The calibration parameter C4 is an extended function parameter. Pr. 30 must be set to "1". (2) Adjusting a deviation of the highest frequency from the Pr. 38 (Pr. 39) setting. (2)-1 Making adjustment with a voltage applied directly across terminals 2-5 (with a current flowing across terminals 4-5) Operation...
  • Page 104 Explanation of functions (parameters) (2)-2 Making adjustment at any point with a voltage not applied across terminals 2-5 (without a current flowing across terminals 4-5) Operation Display Confirm the RUN indication and operation mode indication. The inverter must be at a stop. The inverter must be in the PU operation mode.
  • Page 105: Start-Time Earth (Ground) Fault Detection Selection (Pr. 40 )

    Output terminal function 2.3.19 Start-time earth (ground) fault detection selection (Pr. 40 You can choose whether to make earth (ground) fault detection at start valid or invalid. Earth (Ground) fault detection is executed only right after the start signal is input to the inverter.
  • Page 106: Output Frequency Detection (Pr. 42 , Pr. 43 )

    Output terminal function 2.4.2 Output frequency detection (Pr. 42 , Pr. 43 The output frequency detection signal (FU) is Pr.42 Forward output when the output rotation frequency reaches or Time exceeds the setting. This Reverse rotation function can be used for Pr.43 Output electromagnetic brake...
  • Page 107: Current Detection Function

    Current detection function 2.5 Current detection function 2.5.1 Output current detection functions (Pr. 48 , Pr. 49 If the output remains higher than the Output current Pr. 48 setting during inverter operation 100ms detection for longer than the time set in Pr. 49, signal (Y12) the output current detection signal (Y12) is output from the inverter's open...
  • Page 108: Zero Current Detection (Pr. 50 , Pr. 51 )

    Current detection function 2.5.2 Zero current detection (Pr. 50 , Pr. 51 When the inverter's Start signal output current falls Pr.50 to "0[A]", torque will "zero not be generated. current Output Pr.50 This may cause a detection 100ms current 0 [A] gravity drop when level"...
  • Page 109: Display Function

    Display function 2.6 Display function 2.6.1 Monitor display (Pr. 52 , Pr. 54 You can choose the display of the operation panel "monitor/frequency setting screen". Factory Setting Parameter Name Remarks Setting Range Operation panel display data 0, 1, 100 selection Setting is enabled when Pr.
  • Page 110: Setting Dial Function Selection (Pr. 53 )

    Display function 2.6.2 Setting dial function selection (Pr. 53 You can use the dial like a potentiometer to perform operation. Factory Setting Parameter Name Remarks Setting Range 0: Setting dial frequency setting Setting is Frequency setting 0, 1 mode enabled when operation selection 1: Setting dial Pr.
  • Page 111: Monitoring Reference (Pr. 55 , Pr. 56 )

    Restart operation function 2.6.3 Monitoring reference (Pr. 55 , Pr. 56 Set the frequency 1440 pulses/s (terminal FM) 1440 pulses/s (terminal FM) or current which is referenced when the output frequency or output current is selected for the terminal FM. Output Output Pr.55...
  • Page 112 Restart operation function <Setting> Refer to the following table and set the parameters: Parameter Setting Description 0.1K to 1.5K Coasting time of 0.5s Generally, this setting will pose no problems. 2.2K, 3.7K Coasting time of 1.0s Waiting time for inverter-triggered restart after power is restored from an instantaneous power failure.
  • Page 113 Restart operation function REMARKS •When the start signal is turned off during power failure and power is restored Without speed search (H6=1): Decelerates to stop after running in the same direction before power failure. Note that the motor will coast if the start signal is turned off during restart operation.
  • Page 114: Additional Function

    Additional function 2.8 Additional function 2.8.1 Remote setting function selection (Pr. 59 Even if the operation panel is located away from the enclosure, you can use contact signals to perform continuous variable-speed operation, without using analog signals. When Pr. 59="2" When Pr.
  • Page 115 Additional function <Setting> Operation Pr. 59 Setting Frequency setting storage Remote setting function function (EEPROM) ⎯⎯ •Use Pr. 59 to select whether the remote setting function is used or not and whether the frequency setting storage function* in the remote setting mode is used or not. When "remote setting function - yes"...
  • Page 116 Additional function <Frequency setting storage conditions> •The frequency at which the start signal (STF or STR) turns off is stored. •The remotely-set frequency is stored every one minute after one minute has elapsed since turn off (on) of both the RH (acceleration) and RM (deceleration) signals. (The frequency is written if the present frequency setting compared with the past frequency setting every one minute is different.) (The state of the RL signal dose not affect writing.)
  • Page 117 Additional function CAUTION •The range of frequency changeable by RH (acceleration) and RM (deceleration) is 0 to maximum frequency (Pr. 1 setting). Note that the maximum value of set frequency is (main speed + maximum frequency). (Hz) The set frequency is clamped at (main speed + Pr. 1) Output frequency is Set frequency clamped at Pr.
  • Page 118: Terminal Function Selection

    Terminal function selection 2.9 Terminal function selection 2.9.1 Input terminal function selection (Pr. 60 , Pr. 61 Pr. 62 , Pr. 63 Use these parameters to select/change the input terminal functions. Factory Parameter Name Setting Range Remarks Setting RL terminal function selection RM terminal function 0 to 10, 14, 16...
  • Page 119 Terminal function selection <Setting> Refer to the following table and set the parameters: Signal Setting Functions Related Parameters Name Low-speed run Pr. 4 to Pr. 6, Pr. 24 to Pr. 27, Pr. 59 = "0" command Pr. 80 to Pr. 87 Remote setting Pr.
  • Page 120: Output Terminal Function Selection (Pr. 64 , Pr. 65 )

    Terminal function selection 2.9.2 Output terminal function selection (Pr. 64 , Pr. 65 You can change the functions of the open collector output terminal and contact output terminal. Factory Parameter Name Setting Range Remarks Setting RUN terminal function 0, 1, 3, 4, 11 to selection 16, 93, 95, 98, 99 Setting is enabled when Pr.
  • Page 121: Operation Selection Function

    Operation selection function 2.10 Operation selection function 2.10.1 Retry function (Pr. 66 , Pr. 67 , Pr. 68 , Pr. 69 When any protective function (major fault) is activated and the inverter stops its output, the inverter itself resets automatically and performs retries. Whether retry is performed or not, alarms for retry, number of retries made and waiting time can be selected.
  • Page 122 Operation selection function CAUTION •The cumulative number in Pr. 69 is incremented by "1" when retry operation is regarded as successful, i.e. when normal operation is continued without the protective function (major fault) activated during a period four times longer than the time set in Pr.
  • Page 123: Pwm Carrier Frequency And Long Wiring Mode (Pr. 70 , Pr. 72 )

    Operation selection function 2.10.2 PWM carrier frequency and long wiring mode (Pr. 70 , Pr. 72 You can change the motor sound. Factory Setting Parameter Name Remarks Setting Range Soft-PWM setting 0, 1, 10, 11 Setting is enabled when PWM frequency selection 0 to 15 Pr.
  • Page 124: Voltage Input Selection (Pr. 73 )

    Operation selection function 2.10.3 Voltage input selection (Pr. 73 You can change the input (terminal 2) specifications according to the frequency setting voltage signal. When entering 0 to 10VDC, always make this setting. Factory Setting Parameter Name Remarks Setting Range Terminal 2 input voltage 0-5V/0-10V Setting is enabled...
  • Page 125: Input Filter Time Constant (Pr. 74 )

    Operation selection function 2.10.4 Input filter time constant (Pr. 74 You can set the input section's built-in filter constant for an external voltage or current frequency setting signal. Effective for eliminating noise in the frequency setting circuit. Factory Setting Parameter Name Remarks Setting...
  • Page 126 Operation selection function (1) How to make a restart after a stop by the input from the STOP RESET operation panel (Restarting method with shown) 1. After completion of deceleration to a stop, switch off the STF or STR signal. 2.
  • Page 127: Cooling Fan Operation Selection (Pr. 76 )

    Operation selection function CAUTION Do not reset the inverter with the start signal on. Otherwise, the motor will start instantly after resetting, leading to potentially hazardous conditions. 2.10.6 Cooling fan operation selection (Pr. 76 You can control the operation of the cooling fan built in the inverter (whether there is a cooling fan or not depends on the model.).
  • Page 128: Parameter Write Disable Selection (Pr. 77 )

    Operation selection function 2.10.7 Parameter write disable selection (Pr. 77 You can select between write-enable and disable for parameters. This function is used to prevent parameter values from being rewritten by incorrect operation. Factory Setting Parameter Name Remarks Setting Range Parameter write disable 0, 1, 2 Setting is enabled when Pr.
  • Page 129: Reverse Rotation Prevention Selection (Pr. 78 )

    Operation selection function 2.10.8 Reverse rotation prevention selection (Pr. 78 This function can prevent reverse rotation faults resulting from the incorrect input of the start signal. POINT Used for a machine which runs only in one direction, e.g. fan, pump. (The setting of this function is valid for the combined, PU, external and communication operations.) Factory...
  • Page 130 Operation selection function <Setting> In the following table, operation using the operation panel or parameter unit is abbreviated to PU operation. Pr. 79 Function LED Indication * Setting PU EXT At power on, the inverter is put in the external operation mode.
  • Page 131 Operation selection function (1) PU operation interlock The PU operation interlock function is designed to forcibly change the operation mode to external operation mode when the MRS signal switches off. This function prevents the inverter from being inoperative by the external command if the mode is accidentally left unswitched from PU operation mode.
  • Page 132 Operation selection function REMARKS •If the MRS signal is on, the operation mode cannot be switched to the PU operation mode when the start signal (STF, STR) is on. *1. The operation mode switches to the external operation mode independently of whether the start signal (STF, STR) is on or off.
  • Page 133: Pid Control (Pr. 88 To Pr. 94 )

    Operation selection function 2.10.10 PID control (Pr. 88 to Pr. 94 The inverter can be used to exercise process control, e.g. flow rate, air volume or pressure. The voltage input signal (0 to +5V or 0 to +10V) or Pr. 93 setting is used as a set point and the 4 to 20mADC current input signal used as a feedback value to constitute a feedback system for PID control.
  • Page 134 Operation selection function 2) PD action [Operation example for proportional changes of measured value] A combination of proportional control action (P) and differential control action Set point (D) for providing a manipulated variable in response to deviation speed Deviation Measured to improve the transient characteristic.
  • Page 135 Operation selection function 5) Forward action [Cooling] Increases the manipulated X>0 variable (output frequency) if Set point X<0 deviation X = (set point - Feedback signal measured value) is negative, (Measured value) and decreases the manipulated Measured value variable if deviation is positive. Set point Too cold down...
  • Page 136 Operation selection function (4) I/O signals Signal Terminal Used Function Description Depending on PID control Turn on X14 to exercise PID control. Pr. 60 to Pr. 63 selection Input Set point input Enter the set point for PID control. Measured value Enter the 4 to 20mADC measured value input signal from the detector.
  • Page 137 Operation selection function Parameter Name Setting Description Number Set the upper limit. If the feedback value exceeds the PID upper 0 to 100% setting, the FUP signal is output. (Measured value of limit 4mA is equivalent to 0% and 20mA to 100%.) - - - No function Set the lower limit.
  • Page 138 Operation selection function (7) Calibration example (A detector of 4mA at 0°C and 20mA at 50°C is used to adjust the room temperature to 25°C under PID control. The set point is given to across inverter terminals 2-5 (0-5V).) START ..
  • Page 139 Operation selection function <Set point input calibration> 1. Apply the input voltage of 0% set point setting (e.g. 0V) across terminals 2-5. 2. Make calibration using the calibration parameters C2, C3. At this time, enter in C2 the frequency which should be output by the inverter at the deviation of 0% (e.g. 0Hz).
  • Page 140 Operation selection function REMARKS •If the multi-speed (RH, RM, RL signal) or jog operation (JOG signal) is entered, PID control is stopped and multi-speed or jog operation is started. •Changing the terminal functions using Pr. 60 to Pr. 65 may affect the other functions. Confirm the functions of the corresponding terminals before making settings.
  • Page 141: Auxiliary Function

    Auxiliary function 2.11 Auxiliary function 2.11.1 Slip compensation (Pr. 95 , Pr. 96 , Pr. 97 The inverter output current may be used to assume motor slip to keep the motor speed constant. Factory Parameter Name Setting Range Remarks Setting Rated motor slip - - - 0 to 50%, - - -...
  • Page 142: Automatic Torque Boost Selection (Pr. 98 )

    Auxiliary function 2.11.2 Automatic torque boost selection (Pr. 98 You can choose automatic torque boost control. Automatic torque boost control Not only gives the motor the optimum excitation but also provides high torque even in a low speed range. Factory Setting Parameter Name...
  • Page 143: Motor Primary Resistance (Pr. 99 )

    Maintenance function 2.11.3 Motor primary resistance (Pr. 99 Generally this parameter need not be set. At the factory setting of "- - -", the standard motor constant of the motor capacity set in Pr. 98 (including that of the constant-torque motor) is used. Factory Setting Parameter...
  • Page 144: Current Average Value Monitor Signal (H3, H4, H5)

    Maintenance function 1) H1 (Pr. 503) "maintenance timer" •The cumulative energization time of the inverter is stored into the EEPROM every hour and indicated in 1000h increments. (Cannot be written.) •The maintenance timer is clamped at 999 (999000h). 2) H2 (Pr. 504) "maintenance alarm output set time" •Set the time when the maintenance timer alarm signal (Y95) is output.
  • Page 145 Maintenance function <Pulse operation> The output pulse of the Y93 signal is shown below. From acceleration to constant speed operation Output frequency 1 cycle (20s) Next cycle Y93 signal 5) End pulse 1) Data output mask time Output as low pulse When the speed has changed shape for 1 to 16.5s to constant from...
  • Page 146 Maintenance function 4) Output of maintenance timer value (additional parameter H1) After the output current average value is output as low pulse shape, the maintenance timer value is output as high pulse shape. The output time of the maintenance timer value is obtained from the following calculation. Maintenance timer value (H1×1000h) ×...
  • Page 147: Brake Parameters (Fr-S520E-0.4K To 3.7K Only)

    Brake parameters (FR-S520E-0.4K to 3.7K only) 2.13 Brake parameters (FR-S520E-0.4K to 3.7K only) 2.13.1 Regenerative braking operation (b1 , b2 When making frequent starts/stops in the FR-S520E-0.4K to 3.7K inverter, use the optional brake resistor to increase the regenerative brake duty. Para Factory Setting...
  • Page 148: Calibration Parameters

    Calibration parameters 2.14 Calibration parameters 2.14.1 Meter (frequency meter) calibration (C1 By using the operation panel or parameter unit, you can calibrate an analog meter connected to terminal FM to full scale deflection. Terminal FM provides the pulse output. By setting the calibration parameter C1, you can use the parameter to calibrate the analog meter connected to the inverter without providing a calibration resistor.
  • Page 149 Calibration parameters Changing example Deflecting the meter (analog indicator) to full-scale (1mA) at the preset frequency of 60Hz (for frequency setting, refer to the instruction manual (basic).) POINT •The calibration parameters "C1" can be made to be ready by setting "1" (extended function parameter valid) in Pr.
  • Page 150 Calibration parameters REMARKS •Depending on the set value, it may take some time for the needle to move. •If "1" is set in Pr. 30 "extended function display selection", the calibration parameter C1 "FM terminal calibration" can also be set in the external operation mode. •C1 is factory-set to 1mA full-scale or 1440 pulses/s FM output frequency at 60Hz.
  • Page 151: Clear Parameters

    Clear parameters 2.15 Clear parameters 2.15.1 Parameter clear (CLr Initializes the parameter values to the factory settings. Clear the parameters during a stop in the PU operation mode. Factory Setting Parameter Name Remarks Setting Range 0: Clear is not executed. 1: Parameter clear *1 (Calibration parameters C1 to Setting is...
  • Page 152: Communication Parameters

    Communication parameters 2.16 Communication parameters You can perform communication operation from the RS-485 connector of the inverter through RS-485. (1) Operational functions 1) Operation mode switching [Operation mode switching method] Switching by Switching by operation panel computer program /parameter unit (FR-PU04) Computer External link...
  • Page 153 Communication parameters 2) Operation mode-based functions Operation Mode Operation Item External Computer link Location PU operation operation operation Operation panel Enabled Run command or FR-PU04 Enabled (Combined Disabled (start) operation mode) Enabled Running frequency Enabled (Combined Disabled setting operation mode) Monitoring Enabled Enabled...
  • Page 154: Communication Settings (N1 To N7 , N11 )

    Communication parameters 2.16.1 Communication settings (n1 to n7 , n11 Communication-related parameters Factory Setting Reflection Parameter Name Remarks Setting Range Timing n1(331) Communication station number 0 to 31 After reset n2(332) Communication speed 48,96,192 After reset n3(333) Stop bit length 0,1,10,11 After reset n4(334) Parity check presence/ absence...
  • Page 155 Communication parameters <Setting> To make communication between the personal computer and inverter, initialization of the communication specifications must be made to the inverter. If initial setting is not made or there is a setting fault, data transfer cannot be made. *After making the initial setting of the parameters, always reset the inverter.
  • Page 156 Communication parameters <Computer programming> (1) Communication protocol Data communication between the computer and inverter is performed using the following procedure: Data read Computer (Data flow) Inverter Time Inverter (Data flow) Data write Computer REMARKS *1. If a data error is detected and a retry must be made, execute retry operation with the user program.
  • Page 157 Communication parameters (2) Communication operation presence/absence and data format types Communication operation presence/absence and data format types are as follows: Running Parameter Inverter Monitor- Parame- Operation Command Frequency Write Reset ter Read Communication request is sent to the inverter in accordance with the A (A")*1 A (A")*2...
  • Page 158 Communication parameters (3) Data format Data communication between the computer and inverter is made in ASCII code (hexadecimal code). Data format types 1) Communication request data from computer to inverter [Data write] Instruction Inverter Format A Data Waiting station code check time number...
  • Page 159 Communication parameters REMARKS *1. Indicates the control code. (Refer to the table below.) *2. Specify the inverter station numbers between H00 and H1F (stations 0 to 31) in hexadecimal. *3. When communication parameter n7 "waiting time setting" ≠ - - -, create the communication request data without "waiting time"...
  • Page 160 Communication parameters 5) Waiting time Specify the waiting time between the receipt of data at the inverter from the computer and the transmission of reply data. Set the waiting time in accordance with the response time of the computer between 0 and 150ms in 10ms increments (e.g.
  • Page 161 Communication parameters 7) Signal loss detection (Communication parameter n6 "communication check time interval") · If a signal loss (communication stop) is detected between the inverter and computer as a result of a signal loss detection, a communication error (OPT) occurs and the inverter output is shut off. ·...
  • Page 162 Communication parameters 8) Sum check code The sum check code is 2-digit ASCII (hexadecimal) representing the lower 1 byte (8 bits) of the sum (binary) derived from the checked ASCII data (Example 1) Data check code Computer Inverter 1 E 1 7 A D Binary code ASCII code...
  • Page 163 Communication parameters CAUTION Always set the communication check time interval before starting operation to prevent hazardous conditions. Data communication is not started automatically but is made only once when the computer provides a communication request. If communication is disabled during operation due to signal cable breakage etc., the inverter cannot be stopped.
  • Page 164 Communication parameters <Setting items and set data> After completion of parameter settings, set the instruction codes and data then start communication from the computer to allow various types of operation control and monitoring. Number Instruction Item Description of Data Code Digits H0000: Communication operation Read...
  • Page 165 Communication parameters Number Instruction Item Description of Data Code Digits b0 : b1 : Forward 0 0 0 0 0 0 rotation (STF) [For example 1] b2 : Reverse rotation (STR) * [Example 1] H02 ... Forward rotation b3 : Low speed (RL) * [Example 2] H00 ...
  • Page 166 Communication parameters Number Instruction Item Description of Data Code Digits •When Pr. 37 = "0" (factory setting) The set frequency (RAM or EEPROM) is read. H0000 to H2EE0: 0.01Hz increments Set frequency •When Pr. 37 = "0.1 to 999", expansion link parameter read (RAM) (HFF) = 0 The set speed is read.
  • Page 167 Communication parameters Number Instruction Item Description of Data Code Digits All parameters return to the factory settings. Any of four different all clear operations are performed according to the data. Commu- Calibra Other nication -tion Pr.* Data × H9696 All parameter 4 digits H9966 clear...
  • Page 168 Communication parameters <Error Code List> The corresponding error code in the following list is displayed if an error is detected in any communication request data from the computer: Error Inverter Item Definition Code Operation The number of errors consecutively detected in Computer communication request data from the computer is NAK error...
  • Page 169 Communication parameters (7) Program example To change the operation mode to computer link operation Program Line number Initial setting of I/O file Opening the communication file 10 OPEN"COM1:9600,E,8,2,HD"AS #1 20 COMST1,1,1:COMST1,2,1 ON/OFF setting of circuit control signals (RS, ER) 30 ON COM(1)GOSUB*REC Interrupt definition for data receive 40 COM(1)ON Interrupt enable...
  • Page 170: Operation And Speed Command Source (N8 , N9 )

    Communication parameters 2.16.2 Operation and speed command source (n8 , n9 Used to make valid the run and speed commands from the computer or external terminals. Factory Setting Parameter Name Remarks Setting Range Operation n8 (338) 0, 1 command source Setting is enabled when Pr.
  • Page 171: Link Startup Mode Selection (N10 )

    Communication parameters n8 (Pr. 338) "operation Operation command source" Computer Computer External External location Remarks n9 (Pr. 339) "speed selection command source" Computer External Computer External RH, RM, Remote setting Computer External Computer External (RH, RM, RL) RL, REX Pr. 59 = "1", "2"...
  • Page 172 Communication parameters <Setting> Operation Mode at Pr. 79 Power on or Power Remarks Setting Setting Restoration Can be changed to the computer link operation External operation mode mode by RS-485 communication. PU operation mode Operation mode cannot be changed. Can be changed to the computer link operation External operation mode mode by RS-485 communication.
  • Page 173: Eeprom Write Selection (N12 )

    Communication parameters 2.16.4 EEPROM write selection (n12 You can choose whether the parameters are stored into the EEPROM or not at the parameter setting for computer communication. When performing parameter write frequently, write them to the RAM. Factory Setting Parameter Name Remarks Setting...
  • Page 174: Parameter Unit (Fr-Pu04) Setting

    Parameter unit (FR-PU04) setting 2.17 Parameter unit (FR-PU04) setting When the optional parameter unit (FR-PU04) is connected to the RS-485 connector of the inverter, you can make the environment setting of the parameter unit. CAUTION When the parameter unit (FR-PU04) is used, operation from the operation panel STOP is not accepted.
  • Page 175: Pu Contrast Adjustment (N15 )

    Parameter unit (FR-PU04) setting 2.17.3 PU contrast adjustment (n15 By setting the communication parameter n15 "PU contrast adjustment", you can adjust the LCD contrast of the parameter unit (FR-PU04). When using the FR- PU04, adjust the numerical value to any darkness with the and define that brightness with the of the parameter unit.
  • Page 176: Disconnected Pu Detection/Pu Setting Lock Selection (N17 )

    Parameter unit (FR-PU04) setting 2.17.5 Disconnected PU detection/PU setting lock selection (n17 You can choose the connector disconnection detection function of the parameter unit (FR-PU04) and the control source of the PU (operation panel, FR-PU04). Disconnected PU detection : This function detects that the parameter unit (FR-PU04) has been disconnected from the inverter for longer than 1s and causes the inverter to provide an alarm output (PUE) and come to an alarm stop.
  • Page 177: Caution

    Parameter unit (FR-PU04) setting <Setting> n17 Setting Disconnected PU Detection PU Setting Lock* Operation is continued as-is if the PU is disconnected (without disconnected PU detection) Parameter unit (FR- PU04) is valid Inverter output is shut off when the PU is disconnected (with disconnected PU detection) Operation is continued as-is if the PU is disconnected Operation panel is...
  • Page 178 MEMO...
  • Page 179: Protective Functions

    PROTECTIVE FUNCTIONS This chapter explains the "protective functions" of this product. Always read the instructions before using the equipment. 3.1 Errors (Alarms) ............ 170 3.2 Troubleshooting ..........181 3.3 Precautions for maintenance and inspection... 184 Chapter 1 Chapter 2 Chapter 3 Chapter 4...
  • Page 180: Errors (Alarms)

    Errors (Alarms) 3.1 Errors (Alarms) When an alarm occurs in the inverter, the protective function is activated bringing the inverter to an alarm stop and the PU display automatically changes to any of the following error (alarm) indications. If your fault does not correspond to any of the following errors or if you have any other problem, please contact your sales representative.
  • Page 181: Error (Alarm) Definitions

    Errors (Alarms) 3.1.1 Error (alarm) definitions (1) Major failures When the protective function is activated, the inverter output is shut off and the alarm is output. Operation Panel Indication FR-PU04 OC During Acc Name Overcurrent shut-off during acceleration When the inverter output current reaches or exceeds approximately 200% of the rated inverter current during Description acceleration, the protective circuit is activated to stop the inverter...
  • Page 182 Errors (Alarms) Operation Panel Indication FR-PU04 OV During Acc Name Regenerative overvoltage shut-off during acceleration When the main circuit DC voltage in the inverter rises to or above the specified value due to excessive regenerative energy during Description acceleration, the protective circuit is activated to stop the inverter output.
  • Page 183 Errors (Alarms) Operation Panel Indication FR-PU04 Motor Ovrload Name Motor overload shut-off (electronic thermal relay function) (* 1) The electronic thermal relay function in the inverter detects motor overheat due to overload or reduced cooling capability during low- speed operation to stop the inverter output. When a multi-pole Description motor or two or more motors are run, provide a thermal relay on the output side of the inverter.
  • Page 184 Errors (Alarms) Operation Panel Indication FR-PU04 Ground Fault Name Start-time output side earth (ground) fault overcurrent This function stops the inverter output if an earth (ground) fault overcurrent flows due to an earth (ground) fault which occurred on Description the inverter's output (load) side. Made valid when Pr. 40 "start-time earth (ground) fault detection selection"...
  • Page 185 Errors (Alarms) Operation Panel Indication FR-PU04 Corrupt Memory Name Parameter storage device alarm A fault occurred in parameters stored Description (example: EEPROM fault). Check point Check for too many number of parameter write times. Corrective action Please contact your sales representative. Operation Panel Indication FR-PU04 PU Leave Out...
  • Page 186 Errors (Alarms) (3) Warnings Operation Panel Indication FR-PU04 Name Stall prevention (overcurrent) If a current of more than 150% (* 3) of the rated inverter current flows in the motor, this function stops the increase in frequency until the overload During current decreases to prevent the inverter from acceleration...
  • Page 187 Errors (Alarms) Operation Panel Indication FR-PU04 Name PU stop Pr. 75 "reset selection/PU stop selection" had been set and a stop STOP was made by pressing the of the operation panel or Description RESET parameter unit (FR-PU04) during operation in the external operation mode.
  • Page 188 Errors (Alarms) (4) Write errors Operation Panel Indication FR-PU04 Control Mode Name Write disable error • Write was performed with "1" (write disable) set in Pr. 77 "parameter write disable selection". Description • Frequency jump setting range overlapped. • Parameter write was performed though the operation panel does not have the write precedence.
  • Page 189: To Know The Operating Status At The Occurrence Of Alarm (Only When Fr-Pu04 Is Used)

    Errors (Alarms) 3.1.2 To know the operating status at the occurrence of alarm (only when FR-PU04 is used) When any alarm has occurred, the display automatically switches to the indication of the corresponding protective function (error). By pressing the at this point without resetting the inverter, the display shows the output frequency.
  • Page 190: Checking Of The Alarm History

    Errors (Alarms) 3.1.5 Checking of the alarm history Parameter setting Monitor/frequency setting At powering on MODE Press Return MODE Press MODE MODE [Operation for displaying alarm history] Four past alarms can be displayed by turning the setting dial (The lastest alarm is ended by ".".)  ...
  • Page 191: Troubleshooting

    Troubleshooting 3.2 Troubleshooting POINTS If the cause is still unknown after every check, it is recommended to initialize the parameters (return to factory setting) then reset the required parameter values and check again. 3.2.1 Motor remains stopped 1) Check the main circuit Check that a proper power supply voltage is applied (operation panel display is provided).
  • Page 192: Motor Rotates In Opposite Direction

    Troubleshooting 3.2.2 Motor rotates in opposite direction Check that the phase sequence of output terminals U, V and W is correct. Check that the start signals (forward rotation, reverse rotation) are connected properly. Check the setting of Pr. 17 "RUN key rotation direction selection". 3.2.3 Speed greatly differs from the setting Check that the frequency setting signal is correct.
  • Page 193: Operation Mode Is Not Changed Properly

    Troubleshooting 3.2.8 Operation mode is not changed properly If the operation mode does not change correctly, check the following: 1. External input signal .... Check that the STF or STR signal is off. When it is on, the operation mode cannot be changed.
  • Page 194: Precautions For Maintenance And Inspection

    Precautions for maintenance and inspection 3.3 Precautions for maintenance and inspection The inverter is a static unit mainly consisting of semiconductor devices. Daily inspection must be performed to prevent any fault from occurring due to the adverse effects of the operating environment, such as temperature, humidity, dust, dirt and vibration, changes in the parts with time, service life, and other factors.
  • Page 195: Insulation Resistance Test Using Megger

    Precautions for maintenance and inspection 3.3.4 Insulation resistance test using megger 1) Before performing the insulation resistance test on the external circuit, disconnect the cables from all terminals of the inverter so that the test voltage is not applied to the inverter.
  • Page 196: Daily And Periodic Inspection

    Precautions for maintenance and inspection 3.3.6 Daily and periodic inspection Interval Corrective Inspection Inspection Item Action at Alarm Item Occurrence Check the ambient temperature, Surrounding Improve humidity, dirt, corrosive gas, oil environment emvironment mist, etc Check alarm Check for unusual vibration and Overall unit location and noise...
  • Page 197 Precautions for maintenance and inspection Interval Corrective Inspection Inspection Item Action at Alarm Item Occurrence (1) Check that the output voltages Contact the across phases with the inverter manufacturer operated alone is balanced Operation (2) Check that no fault is found in check Contact the protective and display circuits in...
  • Page 198: Checking The Inverter And Converter Module

    Precautions for maintenance and inspection 3.3.7 Checking the inverter and converter module <Preparation> (1) Disconnect the external power supply cables (R, S, T) and motor cables (U, V, W). (2) Prepare a tester. (Use 100Ω range). <Checking method> Change the polarity of the tester alternately at the inverter terminals R, S, T, U, V, W, P and N, and check for continuity.
  • Page 199: Replacement Of Parts

    Precautions for maintenance and inspection 3.3.8 Replacement of parts The inverter consists of many electronic parts such as semiconductor devices. The following parts may deteriorate with age because of their structures or physical characteristics, leading to reduced performance or fault of the inverter. For preventive maintenance, the parts must be replaced periodically.
  • Page 200 Precautions for maintenance and inspection (1) Cooling fan The cooling fan is used to cool heat-generating parts such as the main circuit semiconductors. The life of the cooling fan bearing is usually 10,000 to 35,000 hours. Hence, the cooling fan must be replaced every 2 to 3 years if the inverter is run continuously.
  • Page 201 Precautions for maintenance and inspection (2) Smoothing capacitors A large-capacity aluminum electrolytic capacitor is used for smoothing in the main circuit DC section, and an aluminum electrolytic capacitor is used for stabilizing the control power in the control circuit. Their characteristics are deteriorated by the adverse effects of ripple currents, etc.
  • Page 202: Measurement Of Main Circuit Voltages, Currents And Powers

    Precautions for maintenance and inspection 3.3.9 Measurement of main circuit voltages, currents and powers • Measurement of voltages and currents Since the voltages and currents on the inverter power supply and output sides include harmonics, measurement data depends on the instruments used and circuits measured.
  • Page 203 Precautions for maintenance and inspection Measuring Points and Instruments Measuring Measuring Remarks Item Point Instrument (Reference Measurement Value) Commercial power supply Power supply Across R-S, Moving-iron Within permissible AC voltage voltage S-T, T-R type AC voltmeter fluctuation (Refer to page 196.) Power supply side R, S, and T Moving-iron...
  • Page 204 Precautions for maintenance and inspection Measuring Measuring Remarks Item Point Instrument (Reference Measurement Value) Moving-coil type Across STF, (Tester and such may When open Start signal STR, RH, RM, be used) 20 to 30VDC Select signal RL-SD (Internal resistance: ON voltage: 1V or less Ω...
  • Page 205: Specifications

    4. SPECIFICATIONS This chapter provides the "specifications" of this product. Always read the instructions before using the equipment 4.1 Specification list ..........196 4.2 Outline dimension drawings ......202 Chapter 1 Chapter 2 Chapter 3 Chapter 4...
  • Page 206: Specification List

    Specification list 4.1 Specification list 4.1.1 Ratings (1) Three-phase 200V power supply 0.75 Type FR-S520E- K (-C) Applied motor capacity (kW) (*1) 0.75 Rated capacity (kVA) (*2) Rated current (A) 16.5 Overload current rating (*3) 150% 60s, 200% 0.5s (inverse time characteristics) Voltage (*4) Three-phase 200 to 240V Rated input AC voltage/frequency...
  • Page 207 Specification list (2) Three-phase 400V power supply 0.75 Type FR-S540E- K Applied motor capacity (kW) (*1) 0.75 Rated capacity (kVA) (*2) Rated current (A) Overload current rating (*3) 150% 60s, 200% 0.5s (Inverse time characteristics) Voltage (*4) Three phase, 380V to 480V Rated input AC voltage/frequency Three phase, 380V to 480V 50Hz/60Hz Permissible AC voltage fluctuation...
  • Page 208 Specification list (3) Single-phase 200V power supply 0.75 Type FR-S520SE- K Applied motor capacity (kW) (*1) 0.75 Rated capacity (kVA) (*2) Rated current (A) Overload current rating (*3) 150% 60s, 200% 0.5s (Inverse time characteristics) Voltage (*4) Three phase, 200V to 240V Rated input AC voltage/frequency Single-phase, 200V to 240V 50Hz/60Hz Permissible AC voltage fluctuation...
  • Page 209 Specification list (4) Single-phase 100V power supply 0.75 Type FR-S510WE- K Applied motor capacity (kW) (*1) 0.75 Rated capacity (kVA) (*2) Rated current (A) Overload current rating (*3) 150% 60s, 200% 0.5s (Inverse time characteristics) Voltage Three phase, 200V to 230V (*4, 6) Rated input AC voltage/frequency Single-phase, 100V to 115V 50Hz/60Hz Permissible AC voltage fluctuation...
  • Page 210: Common Specifications

    Specification list Common specifications 4.1.2 Selectable between Soft-PWM control and high carrier Control method frequency PWM control, selectable between V/F control and automatic torque boost control. 0.5 to 120Hz (starting frequency variable between 0 and Output frequency range 60Hz) 5VDC input: 1/500 of max. set frequency, Frequency setting resolution 10VDC, 4 to 20mADC input: 1/1000 of max.
  • Page 211 Specification list Maximum and minimum frequency settings, frequency jump operation, external thermal relay input selection, automatic Operational restart after instantaneous power failure, forward/reverse functions rotation prevention, slip compensation, operation mode selection, PID control, computer link operation (RS-485). 1 open collector signal can be selected from among inverter running, up-to-frequency, frequency detection, overload warning, zero current detection, output current detection, PID...
  • Page 212: Outline Dimension Drawings

    Outline dimension drawings 4.2 Outline dimension drawings •FR-S520E-0.1K, 0.2K, 0.4K, 0.75K •FR-S520SE-0.1K, 0.2K, 0.4K, 0.75K •FR-S510WE-0.1K, 0.2K, 0.4K φ5 hole Rating plate 18.5 •Three-phase 200V power supply Capacity 0.1K,0.2K 80.5 0.4K 112.5 0.75K 132.5 •Single-phase 200V power supply Capacity 0.1K,0.2K 80.5 0.4K 142.5...
  • Page 213 Outline dimension drawings •FR-S520E-1.5K, 2.2K, 3.7K •FR-S540E-0.4K, 0.75K, 1.5K, 2.2K, 3.7K •FR-S520SE-1.5K •FR-S510WE-0.75K φ5 hole Rating plate Cooling fan×1 18.5 •Three-phase 200V power supply Capacity 1.5K,2.2K 135.5 3.7K 142.5 •Three-phase 400V power supply Capacity 0.4K,0.75K 129.5 1.5K 135.5 2.2K 155.5 3.7K 165.5 •Single-phase 200V power supply...
  • Page 214 Outline dimension drawings •Parameter unit (FR-PU04) <Outline drawing> <Panel cut dimension drawing> 16.5 23.75 10.5 11.75 5- 4 hole 1.25 5-M3 hole Effective depth 4.5 (Unit:mm) Choose the mounting screws whose length will not exceed the effective depth of the mounting threads.
  • Page 215: Appendix

    APPENDIX APPENDIX 1 Parameter instruction code list ..206...
  • Page 216: Appendix 1 Parameter Instruction Code List

    Parameter instruction code list APPENDIX 1 Parameter instruction code list Instruction Link Parameter Computer Code Extension Func- Parameter Link Data Name Setting tion Number Setting Read Write (Instruction Increments* Code 7F/FF) Torque boost 0.1% Maximum frequency 0.01Hz Minimum frequency 0.01Hz Base frequency 0.01Hz Multi-speed setting (high...
  • Page 217 Parameter instruction code list Instruction Computer Link Parameter Func- Parameter Code Link Data Extension Setting Name tion Number Setting (Instruction Read Write Increments * Code 7F/FF) Stall prevention operation level compensation factor 0.1% at double speed Multi-speed setting 0.01Hz (speed 4) Multi-speed setting 0.01Hz (speed 5)
  • Page 218 Parameter instruction code list Instruction Computer Link Parameter Func- Parameter Code Link Data Extension Setting Name tion Number Setting (Instruction Read Write Increments * Code 7F/FF) Operation panel display data selection Frequency setting operation selection FM terminal function selection Frequency monitoring 0.01Hz reference Current monitoring...
  • Page 219 Parameter instruction code list Instruction Computer Link Parameter Func- Parameter Code Link Data Extension Setting Name tion Number Setting (Instruction Read Write Increments * Code 7F/FF) Multi-speed setting 0.01Hz (speed 8) Multi-speed setting 0.01Hz (speed 9) Multi-speed setting 0.01Hz (speed 10) Multi-speed setting 0.01Hz (speed 11)
  • Page 220 Parameter instruction code list Instruction Computer Link Parameter Func- Parameter Code Link Data Extension Setting Name tion Number Setting (Instruction Read Write Increments * Code 7F/FF) Automatic restart after H6 (162) instantaneous power failure selection Second electronic H7 (559) 0.01A thermal O/L relay Regenerative function b1 (560)
  • Page 221 Parameter instruction code list Instruction Computer Link Parameter Func- Parameter Code Link Data Extension Setting Name tion Number Setting (Instruction Read Write Increments * Code 7F/FF) Communication station n1 (331) number n2 (332) Communication speed n3 (333) Stop bit length Parity check presence/ n4 (334) absence...
  • Page 222 REVISIONS *The manual number is given on the bottom left of the back cover. Print Date Revision Manual Number Jun., 2003 IB(NA)-0600152E-A First edition Sep., 2004 IB(NA)-0600152E-B Addition Three phase 400V power input specification, single phase 200V power input specification, single phase 100V power input specification Jun., 2007 IB(NA)-0600152E-C...

Table of Contents