Installation

4.3 Mounting the interface module

4.3
Mounting the interface module
Prerequisites
● The terminating module is removed from the interface module.
● Required tool: cross-tip screwdriver, size 2.
Procedure
Proceed as follows to mount the interface module:
1. Snap-mount the Interface module onto the rack, then slide it into the correct position
2. Screw-mount the Interface module onto the rack.
Interface module for PROFIBUS DP (without connection module):
2 recessed head screws on the front: top and bottom, tightening torque 1.5 Nm
Interface module for PROFINET PN:
All recessed head screws on the front: top and bottom, tightening torque 1.5 Nm
The PROFIBUS interface module is shown in the following figure.
Figure 4-4
You have mounted the interface module.
34
Mounting the interface module
SIMATIC ET 200pro FC-2 converter
Operating Instructions, 04/2015, FW V4.7.3, A5E34257324B AB