Procedure with enabled safety functions
To load the settings from the PG to the inverter and to activate the safety functions, proceed
as follows:
1. Go online with STARTER :
2. Select the button "Download project to target system":
3. Call the STARTER screen form for the safety functions.
You have transferred the settings from the PG to the inverter.
To activate the safety functions, proceed as follows:
1. Select the "Copy parameter" button.
2. Press the "Activate settings" button.
3. To save the data in the inverter, select the "Copy RAM to ROM" button:
4. Go offline with STARTER :
5. Switch off the inverter power supply.
6. Wait until all LED on the inverter go dark.
7. Switch on the inverter power supply again. Your settings only become effective after this
power-on reset.
You have transferred the settings from the PG to the inverter and have activated the safety
functions.
SIMATIC ET 200pro FC-2 converter
Operating Instructions, 04/2015, FW V4.7.3, A5E34257324B AB
Backing up data and series commissioning
.
.
9.2 Saving settings on a PC
.
.
173