2.
3.
4.
5th
6th
7th
8th Set the check mark for "RAM to
ROM (save data in the drive)" to
save your data in the inverter so
that it is not lost when the power
fails.
Exit basic commissioning.
You have entered all of the data that is necessary for the basic commissioning of your
inverter.
SIMATIC ET 200pro FC-2 converter
Operating Instructions, 04/2015, FW V4.7.3, A5E34257324B AB
Select the application for the inverter:
Low overload for applications that only require a low dynamic perfor-
mance, e.g. pumps or fans.
High overload for applications requiring a high dynamic performance, e.g.
conveyor systems.
Select your motor.
Enter the motor data according to the rating plate of your motor.
If you have selected a motor based on its article number, the data has
already been entered.
If you have set the "Speed control" control mode, then we recommend
setting "[1] Identify motor data at standstill and with motor rotating".
With this setting,
the inverter opti-
mizes its speed
controller.
If one of the following cases is applicable, select the setting "[2] Identify
motor data at standstill":
• You have selected "Speed control" as control mode, however the
motor cannot freely rotate, e.g. for mechanically limited traversing
sections.
• You have set "V/f control" as control mode.
Set the most important parameters to suit your application.
We recommend
the setting "Calcu-
late motor data
only".
Commissioning
6.5 Basic commissioning
81