10.1 Replacing the ET 200pro FC-2
8.
Reconnect the three HANQ cables to the converter.
Note:
Ensure that the correct cables are connected to the correct
inputs
9.
Switch on the mains supply to the converter.
10.
For converters with no safety functions enabled
The converter will read the parameter settings from the memory card after power-up.
If the converter outputs the Alarm A01028, this indicates that the parameter settings are not compatible with the
converter.
If Alarm A01028 is present, clear the alarm by setting parameter p0971 to 1 and recommission the converter.
When recommissioned, if the alarm A01028 is not present after the power-cycle of the converter the new param-
eter settings have been accepted.
For converters with safety functions enabled
The converter will read the parameter settings from the memory card after power-up.
If the converter outputs the Alarm A01028, this indicates that the parameter settings are not compatible with the
converter.
If Alarm A01028 is present, clear the alarm by setting parameter p0971 to 1 and recommission the converter.
When recommissioned, if the alarm A01028 is not present after the power-cycle of the converter the new param-
eter settings have been accepted.
Perform a reduced acceptance test as described in the following procedure.
You have now replaced the converter.