5.3

Configure the hardware in SIMATIC Manager

5.3.1

Configure the inverter on PROFIBUS in SIMATIC Manager

Description
The following example of an ET 200pro FC-2 frequency converter with "IM 154-2 DP HF"
interface module demonstrates the three steps in creating a PROFIBUS configuration in HW
Config of SIMATIC Manager.
● Parameterizing the PROFIBUS DP interface in HW Config
● Equipping a ET 200pro station
● Settings for the frequency converter
Note
Please refer to the "Interface modules" chapter in Manual, "ET 200pro distributed I/O
system" for information on the interface modules.
Parameterizing the PROFIBUS DP interface in HW Config
The hardware configuration is used to parameterize the PROFIBUS DP interface. When a
CPU with an integrated DP interface or a DP communications processor is selected from the
hardware catalog, a PROFIBUS DP system is made available in the hardware configuration.
Once the parameters for the master have been set, the slave - in this case, the ET 200pro
station - must be selected from the hardware catalog and positioned on the PROFIBUS line.
This is done by inserting an IM 154. The PROFIBUS address of the ET 200pro station must
also be specified in the IM 154.
Insert a master system via the context menu of the CPU DP interface.
Figure 5-1
SIMATIC ET 200pro FC-2 converter
Operating Instructions, 04/2015, FW V4.7.3, A5E34257324B AB
Master system
5.3 Configure the hardware in SIMATIC Manager
Configure the hardware
55