Siemens SIMATIC ET 200pro Original Instructions Manual page 228

Distributed i/o system low voltage converter
Hide thumbs Also See for SIMATIC ET 200pro:
Table of Contents

Advertisement

Technical data
12.5 Electromagnetic compatibility of the converters
Table 12- 10 Limit values for interference immunity for general industrial application to EN 61000-6-2
EMC phenomena
Voltage dips
Voltage interruptions
Electrostatic discharge
Interference
Burst
pulses
Voltage surge
High-frequency electromagnetic field,
amplitude-modulated
The requirements of the generic standards in respect of interference immunity are met. The
required values for interference emission are complied with if installation takes place
according to EMC installation guidelines.
228
Basic standard for
Level
test procedures
EN 61000-4-11
30% reduction, 0.5 periods
EN 61000-4-11
> 95% reduction, 250 periods
EN 61000-4-2
8 kV, air discharge
4 kV, contact discharge
EN 61000-4-4
2 kV electric power cable
1 kV control cable
EN 61000-4-5
2 kV electric power cable (phase
- ground)
1 kV electric power cable (phase
- phase)
1 kV control cable (cable -
ground)
EN 61000-4-3
80 MHz – 1000 MHz, 10 V/m,
80 % AM
SIMATIC ET 200pro FC-2 converter
Operating Instructions, 04/2015, FW V4.7.3, A5E34257324B AB
Evaluation criterion
B
C
B
B
B
B
B
B
B
A