Diagnostics with Profinet
PROFINET uses the channel diagnostics to transfer PROFIdrive message classes. See
PROFINET IO specification. To access this link, you must be a member of PROFIBUS and
PROFINET International (PI).
The channel diagnostics has the following structure:
0002 hex
Undervoltage
0003 hex
Overvoltage
0005 hex
Overtemperature
0009 hex
Error
0010 hex
Parameterization error
0013 hex
Communication error
Reading out diagnostics data
The control requests the diagnostics data from the inverter using "Read data set", e.g. using
a read record with index 800C hex.
For details, see PROFINET-IO specification.
SIMATIC ET 200pro FC-2 converter
Operating Instructions, 04/2015, FW V4.7.3, A5E34257324B AB
Alarms, faults and system messages
11.2 Diagnostics through fieldbus
0014 hex
Ground fault
0018 hex
Actuator disconnection
0019 hex
Safety-related shutdown
001A hex
External fault
001D hex
Fault 1 in actuator/sensor
001F hex
Channel temporarily not available
199