Mains connection and line-side power components
3.7 Line filter
3.7.6

Mounting

The external line filters are designed as base components. The line filter is retained on the
mounting surface and the Power Module is mounted on the line filter in a space-saving
fashion. The cables to the Power Modules are already connected at the line filter. The line
filter is connected to the line supply through terminals.
Figure 3-5
Table 3- 10
Frame size
FSA
FSB
FSC
50
PM240-2 Power Module, frame size FSA
Line filter
Shield connection
Installation example: Power Module PM240-2 (frame size FSA) with screening kit and
line filter
Connecting the line filter for the PM240-2 on the mounting surface
Fastening
4 x M4 bolts
4 x M5 bolts
Tightening torque
2.5 Nm
3 Nm
SINAMICS S110
Manual, 07/2015, 6SL3097-4AC10-0BP5